Basic alarm parameters
10.2

Basic time setting for the automatic Timer Reset

10.3

Defining the time interval for alarm zones

72
Siemens Building Technologies
Fire Safety & Security Products
No external alarms:
If this kind of configuration is not in use, select the 'no external alarms'
parameter.
Set master relay in case of alarm:
Programme the alarm master relay here:
on
off
inactive
The time period for an automatic timer reset can be set in seconds (period of time
after which an alarm signal will automatically be turned off). The setting is entered
as a multiple of the basic time. The basic time can be entered here.
Fig. 54
Alarm zone 1...4, 5...8
When setting time enablement, note that the setting will not take immediate effect if the start time for
the day in question already lies in the past. The setting will take effect on the following day at the
earliest.
To test the setting, set the start time to a time that is just a few minutes in the future.
For example:
You want to set and test a time interval of 17:00 to 24:00. It is already 17:10 when you enter the
setting. The time interval would normally only come into effect on the following day as the start time
already lies in the past. For test purposes, set the start time to 17:15, or similar.
Each alarm zone (max. 8) is either
always active
– or –
only active for a set time interval
Enter the desired date, the start time and the stop time for alarm activation here.
All alarms generated by this alarm zone will be ignored, except when alarms are
generated in the set time period.
Enter 00:00 as the time if switching from active to inactive or vice versa takes place
at midnight.