5.7 CONTROL ELEMENTS

PATH: SETTINGS
CONTROL ELEMENTS
 SETTING GROUPS
5
The 61850 standard provides for the ability to monitor, edit, and change setting groups in a relay through a series of ser-
vices operating on Setting Group Control Block values. There is one SGCB in LLN0 in LD1 in the UR as, at present, the
other LDs do not support multiple setting groups The default value of
or UR setting group control to function, the
The active setting group in the UR is settable from either the value set via a FlexLogic operand in the UR (present practice)
or a SelectActiveSG command from a 61850 Client. For both the UR and IEC 61850, the default active setting group is "1".
A 61850 SelectActiveSG command sets one of the internal Non-Volatile flags (61850 SG Level x) that represents the
requested Active Setting Group shown as follows:
Table 5–23: ACTIVE SETTING GROUP
SELECTACTIVESG VALUE
1 (default)
2
3
4
5
6
On power-up or restart, the previously selected 61850 SG Level x is re-instated. Similarly, the input to the setting group
control in the UR can be designed with Non-Volatile latches to achieve the same effect.
The setting groups menu controls the activation and deactivation of up to six possible groups of settings in the
settings menu. The faceplate Settings In Use LEDs indicate which active group (with a non-flashing energized
ELEMENTS
LED) is in service.
5-164
SETTINGS GROUPS

SETTING GROUPS

FUNCTION: Enabled
SETTING GROUPS BLK:
MESSAGE
Off
GROUP 2 ACTIVATE ON:
MESSAGE
Off
GROUP 3 ACTIVATE ON:
MESSAGE
Off
GROUP 6 ACTIVATE ON:
MESSAGE
Off
GROUP 1 NAME:
MESSAGE
GROUP 2 NAME:
MESSAGE
GROUP 6 NAME:
MESSAGE
SETTING GROUP
MESSAGE
EVENTS: Disabled
SETTING GROUPS FUNCTION
FLAG SET
SG Level 1
SG Level 2
SG Level 3
SG Level 4
SG Level 4
SG Level 6
B30 Bus Differential System
Range: Disabled, Enabled
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: up to 16 alphanumeric characters
Range: up to 16 alphanumeric characters
Range: up to 16 alphanumeric characters
Range: Disabled, Enabled
SETTING GROUPS
must be set to Enabled.
5 SETTINGS
5.7.3 SETTING GROUPS
is Disabled. In order for 61850 and/
GROUPED
GE Multilin