2 PRODUCT DESCRIPTION
Table 2–2: OTHER DEVICE FUNCTIONS
FUNCTION
Breaker control
Breaker flashover
Contact inputs (up to 96)
Contact outputs (up to 64)
Control pushbuttons
CyberSentry™ security
Digital counters (8)
Digital elements (48)
Direct inputs and outputs (32)
Disconnect switches
DNP 3.0 or IEC 60870-5-104 protocol
Ethernet Global Data protocol (optional)
The following security features are available:
Password security — Basic security present in the default offering of the product
EnerVista security — Role-based access to various EnerVista software screens and configuration elements. The fea-
ture is available in the default offering of the product and only in the EnerVista software.
CyberSentry security — Advanced security options available as a software option. When purchased, the options are
automatically enabled, and the default Password security and EnerVista security are disabled.
Changing the password, or any other setting, does not take the relay out of service. The relay is taken out of service when
a settings file is written to it.
a) ENERVISTA SECURITY
The EnerVista security management system is a role-based access control (RBAC) system that allows an administrator to
manage the privileges of multiple users. This allows for access control of UR devices by multiple personnel within a substa-
tion and conforms to the principles of RBAC as defined in ANSI INCITS 359-2004. The EnerVista security management
system is disabled by default to allow the administrator direct access to the EnerVista software after installation. It is recom-
mended that security be enabled before placing the device in service.
Basic password or enhanced CyberSentry security applies, depending on purchase.
b) PASSWORD SECURITY
Password security is a basic security feature present in the default offering of the product.
Two levels of password security are provided: command and setting.
The following operations are under command password supervision:
Changing the state of virtual inputs
Clearing the event records
Clearing the oscillography records
Changing the date and time
Clearing the data logger
Clearing the user-programmable pushbutton states
The following operations are under setting password supervision:
Changing any setting
GE Multilin
FUNCTION
Event recorder
FlexElements™ (8)
FlexLogic equations
IEC 61850 communications (optional)
Metering: current, voltage, frequency
Modbus communications
Modbus user map
Non-volatile latches
Non-volatile selector switch
Oscillography
Selector switch
Setting groups (6)
B30 Bus Differential System
2.1 INTRODUCTION
FUNCTION
Teleprotection inputs and outputs
Thermal overload protection
Time synchronization over IRIG-B or
IEEE 1588
Time synchronization over SNTP
Transducer inputs and outputs
User-definable displays
User-programmable fault reports
User-programmable LEDs
User-programmable pushbuttons
User-programmable self-tests
Virtual inputs (64)
Virtual outputs (96)

2.1.2 SECURITY

2