7.1 COMMANDS

PATH: COMMANDS
 COMMANDS
 CLEAR RECORDS
This menu contains commands for clearing historical data such as the event records. Data is cleared by changing a com-
mand setting to "Yes" and pressing the ENTER key. After clearing data, the command setting automatically reverts to "No".

PATH: COMMANDS
 COMMANDS
 SET DATE AND TIME
The date and time can be entered here via the faceplate keypad, but if the relay is synchronizing to an external time source
such as PTP, IRIGB or SNTP, the manually entered time will be quickly over-written. The time setting is based on the 24-
hour clock. The complete date, as a minimum, must be entered to allow execution of this command. The new time (if
entered) and date will take effect at the moment the ENTER key is clicked.
The timescale of the entered time should be local time, including daylight time where and when applicable.
7

PATH: COMMANDS
 COMMANDS
 RELAY MAINTENANCE
This menu contains commands for relay maintenance purposes. Commands for the lamp test and order code are activated
by changing a command setting to "Yes" and pressing the ENTER key. The command setting will then automatically revert
to "No". The service command is activated by entering a numerical code and pressing the ENTER key.
7-2
CLEAR RECORDS
CLEAR USER FAULT
REPORTS? No
CLEAR EVENT RECORDS?
No
CLEAR OSCILLOGRAPHY?
No
CLEAR UNAUTHORIZED
ACCESS? No
CLEAR DIRECT I/O
COUNTERS? No
CLEAR TELEPROTECT
COUNTERS? No
CLEAR ALL RELAY
RECORDS? No
SET DATE AND TIME
SET DATE AND TIME:
2000/01/14 13:47:03

RELAY MAINTENANCE

PERFORM LAMPTEST?
No
UPDATE ORDER CODE?
No
REBOOT RELAY?
No
SERVICE COMMAND:
0
SAVE VOLATILE DATA?
No
B30 Bus Differential System
7 COMMANDS AND TARGETS
7.1.3 CLEAR RECORDS
Range: No, Yes
Range: No, Yes
Range: No, Yes
Range: No, Yes
Range: No, Yes. Valid only for units with Direct Input/
Output module.
Range: No, Yes
Range: No, Yes
7.1.4 SET DATE AND TIME
(YYYY/MM/DD HH:MM:SS)
7.1.5 RELAY MAINTENANCE
Range: No, Yes
Range: No, Yes
Range: No, Yes
Range: 0, 101
Range: No, Yes