GE B30 UR Series Instruction Manual page 166

Bus differential system
Hide thumbs Also See for B30 UR Series:
Table of Contents

Advertisement

5.2 PRODUCT SETUP
IEC 61850 messaging can form part of protection schemes. Consider 61850 settings with the same criticality as
protection element settings. To ensure reliable performance of protection schemes utilizing 61850 messaging, it
can be desirable to route 61850 traffic on a separate port from SCADA communications, or to use redundant, inde-
NOTE
pendent ports, and a high speed network recovery method, such as PRP.
The B30 supports the Manufacturing Message Specification (MMS) protocol as specified by IEC 61850. MMS is supported
over two protocol stacks: TCP/IP over Ethernet. The B30 operates as an IEC 61850 server. The Remote inputs and outputs
section in this chapter describe the peer-to-peer GSSE/GOOSE message scheme.
The GSSE/GOOSE configuration main menu is divided into two areas: transmission and reception.
PATH: SETTINGS
PRODUCT SETUP
 GSSE / GOOSE
 CONFIGURATION
The main transmission menu is shown below:
PATH: SETTINGS
PRODUCT SETUP
TRANSMISSION
 TRANSMISSION
5
The general transmission settings are shown below:
PATH: SETTINGS
PRODUCT SETUP
TRANSMISSION
GENERAL
 GENERAL
The
DEFAULT GSSE/GOOSE UPDATE TIME
put state changes to be sent. When remote output data changes, GSSE or GOOSE messages are sent immediately. This
setting controls the steady-state heartbeat time interval.
The
DEFAULT GSSE/GOOSE UPDATE TIME
The GSSE settings are shown below:
PATH: SETTINGS
PRODUCT SETUP

TRANSMISSION
GSEE
 GSSE
These settings are applicable to GSSE only. If the fixed GOOSE function is enabled, GSSE messages are not transmitted.
5-40

COMMUNICATIONS
 TRANSMISSION
 RECEPTION
MESSAGE

COMMUNICATIONS
 GENERAL
 GSSE
MESSAGE
 FIXED GOOSE
MESSAGE
 CONFIGURABLE
MESSAGE
 GOOSE

COMMUNICATIONS
DEFAULT GSSE/GOOSE
UPDATE TIME: 60 s
sets the time between GSSE or GOOSE messages when there are no remote out-
setting is applicable to GSSE, fixed B30 GOOSE, and configurable GOOSE.

COMMUNICATIONS
GSSE FUNCTION:
Enabled
GSSE ID:
MESSAGE
GSSEOut
DESTINATION MAC:
MESSAGE
000000000000
B30 Bus Differential System

IEC 61850 PROTOCOL
GSSE/GOOSE CONFIGURATION

IEC 61850 PROTOCOL
GSSE/GOOSE CONFIGURATION

IEC 61850 PROTOCOL
GSSE/GOOSE CONFIGURATION
Range: 1 to 60 s in steps of 1

IEC 61850 PROTOCOL
GSSE/GOOSE CONFIGURATION
Range: Enabled, Disabled
Range: 65-character ASCII string
Range: standard MAC address
5 SETTINGS
GE Multilin

Advertisement

Table of Contents
loading

This manual is also suitable for:

B30

Table of Contents