5.2 PRODUCT SETUP
2.
Set the properties for user-programmable pushbutton 1 by making the following changes in the
SETUP
USER-PROGRAMMABLE PUSHBUTTONS
PUSHBUTTON 1 FUNCTION:
PUSHBTN 1 DROP-OUT TIME:
a) MAIN MENU
PATH: SETTINGS
PRODUCT SETUP
COMMUNICATIONS
5
b) SERIAL PORTS
PATH: SETTINGS
PRODUCT SETUP
SERIAL PORTS
The B30 is equipped with two independent serial communication ports. The faceplate RS232 port is intended for local use
and is fixed at 19200 baud and no parity. The rear COM2 port is RS485. The RS485 port has settings for baud rate and par-
ity. It is important that these parameters agree with the settings used on the computer or other equipment that is connected
to these ports. Any of these ports can be connected to a computer running EnerVista UR Setup. This software can down-
load and upload setting files, view measured parameters, and upgrade the relay firmware. A maximum of 32 relays can be
daisy-chained and connected to a DCS, PLC, or computer using the RS485 ports.
5-26
"Self-reset"
"0.20 s"
COMMUNICATIONS
SERIAL PORTS
NETWORK
MESSAGE
ROUTING
MESSAGE
MODBUS PROTOCOL
MESSAGE
DNP PROTOCOL
MESSAGE
DNP / IEC104
MESSAGE
POINT LISTS
IEC 61850 PROTOCOL
MESSAGE
WEB SERVER
MESSAGE
HTTP PROTOCOL
TFTP PROTOCOL
MESSAGE
IEC 60870-5-104
MESSAGE
PROTOCOL
EGD PROTOCOL
MESSAGE
COMMUNICATIONS
RS485 COM2 BAUD
RATE: 19200
RS485 COM2 PARITY:
MESSAGE
None
RS485 COM2 RESPONSE
MESSAGE
MIN TIME:
B30 Bus Differential System
menu:
USER PUSHBUTTON 1
See below.
See page 5–29.
See page 5–31.
See page 5–34.
See page 5–35.
See page 5–38.
See page 5–39.
See page 5–54.
See page 5–54.
See page 5–55.
See page 5–56.
SERIAL PORTS
Range: 300, 1200, 2400, 4800, 9600, 14400, 19200,
28800, 33600, 38400, 57600, 115200
Range: None, Odd, Even
Range: 0 to 1000 ms in steps of 10
0 ms
5 SETTINGS
SETTINGS
PRODUCT
5.2.4 COMMUNICATIONS
8
GE Multilin