GE B30 UR Series Instruction Manual page 262

Bus differential system
Hide thumbs Also See for B30 UR Series:
Table of Contents

Advertisement

5.6 GROUPED ELEMENTS
b) INVERSE TOC CURVE CHARACTERISTICS
The inverse time overcurrent curves used by the time overcurrent elements are the IEEE, IEC, GE Type IAC, and I
dard curve shapes. This allows for simplified coordination with downstream devices.
If none of these curve shapes is adequate, FlexCurves may be used to customize the inverse time curve characteristics.
The definite time curve is also an option that may be appropriate if only simple protection is required.
Table 5–15: OVERCURRENT CURVE TYPES
IEEE
IEEE Extremely Inverse
IEEE Very Inverse
IEEE Moderately Inverse
A time dial multiplier setting allows selection of a multiple of the base curve shape (where the time dial multiplier = 1) with
the curve shape (
CURVE
to the time multiplier (
TD MULTIPLIER
or base curve values. Setting the multiplier to zero results in an instantaneous response to all current levels above pickup.
Time overcurrent time calculations are made with an internal energy capacity memory variable. When this variable indi-
cates that the energy capacity has reached 100%, a time overcurrent element will operate. If less than 100% energy capac-
ity is accumulated in this variable and the current falls below the dropout threshold of 97 to 98% of the pickup value, the
variable must be reduced. Two methods of this resetting operation are available: "Instantaneous" and "Timed". The "Instan-
taneous" selection is intended for applications with other relays, such as most static relays, which set the energy capacity
directly to zero when the current falls below the reset threshold. The "Timed" selection can be used where the relay must
5
coordinate with electromechanical relays.
IEEE CURVES:
The IEEE time overcurrent curve shapes conform to industry standards and the IEEE C37.112-1996 curve classifications
for extremely, very, and moderately inverse. The IEEE curves are derived from the formulae:
where: T = operate time (in seconds), TDM = Multiplier setting, I = input current, I
A, B, p = constants, T
t
= characteristic constant
r
Table 5–16: IEEE INVERSE TIME CURVE CONSTANTS
IEEE CURVE SHAPE
IEEE Extremely Inverse
IEEE Very Inverse
IEEE Moderately Inverse
Table 5–17: IEEE CURVE TRIP TIMES (IN SECONDS)
MULTIPLIER
(TDM)
1.5
IEEE EXTREMELY INVERSE
0.5
11.341
1.0
22.682
2.0
45.363
4.0
90.727
6.0
136.090
8.0
181.454
5-136
IEC
IEC Curve A (BS142)
IEC Curve B (BS142)
IEC Curve C (BS142)
IEC Short Inverse
) setting. Unlike the electromechanical time dial equivalent, operate times are directly proportional
) setting value. For example, all times for a multiplier of 10 are 10 times the multiplier 1
A
--------------------------------- -
B
+
p
I
T
TDM
×
=
--------------- -
1
I
pickup
= reset time in seconds (assuming energy capacity is 100% and
RESET
A
28.2
0.1217
19.61
0.491
0.0515
0.1140
2.0
3.0
4.0
4.761
1.823
1.001
9.522
3.647
2.002
19.043
7.293
4.003
38.087
14.587
8.007
57.130
21.880
12.010
76.174
29.174
16.014
B30 Bus Differential System
GE TYPE IAC
IAC Extremely Inverse
IAC Very Inverse
IAC Inverse
IAC Short Inverse
t
----------------------------------- -
T
TDM
×
,
=
RESET
1
--------------- -
I
pickup
pickup
B
P
T
R
2.0000
29.1
2.0000
21.6
0.02000
4.85
CURRENT ( I / I
)
pickup
5.0
6.0
7.0
0.648
0.464
0.355
1.297
0.927
0.709
2.593
1.855
1.418
5.187
3.710
2.837
7.780
5.564
4.255
10.374
7.419
5.674
5 SETTINGS
OTHER
2
I
t
FlexCurves A, B, C, and D
Recloser Curves
Definite Time
r
I
2
= Pickup Current setting
is "Timed"),
RESET
8.0
9.0
0.285
0.237
0.569
0.474
1.139
0.948
2.277
1.897
3.416
2.845
4.555
3.794
GE Multilin
2
t stan-
(EQ 5.4)
10.0
0.203
0.407
0.813
1.626
2.439
3.252

Advertisement

Table of Contents
loading

This manual is also suitable for:

B30

Table of Contents