GE B30 UR Series Instruction Manual page 173

Bus differential system
Hide thumbs Also See for B30 UR Series:
Table of Contents

Advertisement

5 SETTINGS
The main menu for the IEC 61850 server configuration is shown below.
PATH: SETTINGS
PRODUCT SETUP
 SERVER
 CONFIGURATION
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
The
and
settings represent the MMS domain name (IEC 61850 logical device) where all IEC/MMS logical
IED NAME
LD INST
nodes are located. Valid characters for these values are upper and lowercase letters, numbers, and the underscore (_)
character, and the first character in the string must be a letter. This conforms to the IEC 61850 standard. The
variable string and can be composed of ASCII characters. This string appears within the PhyName of the LPHD node.
The
IEC/MMS TCP PORT NUMBER
setting determines whether or not the "UR" MMS domain will be available. This domain contains a large num-
NON-IEC DATA
ber of UR-series specific data items that are not available in the IEC 61850 logical nodes. This data does not follow the IEC
61850 naming conventions. For communications schemes that strictly follow the IEC 61850 standard, this setting should be
"Disabled".
When a 0 value is involved in a change, the changes to the
B30 is restarted.
NOTE
Do not set more than one protocol to the same TCP/UDP port number, as this results in unreliable operation of
those protocols.
The
feature should be set to "Disabled" when IEC 61850 client/server functionality is not required. IEC
SERVER SCANNING
61850 has two modes of functionality: GOOSE/GSSE inter-device communication and client/server communication. If the
GOOSE/GSSE functionality is required without the IEC 61850 client server feature, then server scanning can be disabled
to increase CPU resources. When server scanning is disabled, there is no updating of the IEC 61850 logical node status
values in the B30. Clients are still able to connect to the server (B30 relay), but most data values are not updated. This set-
ting does not affect GOOSE/GSSE operation.
Changes to the
IED NAME
NOTE
GE Multilin


COMMUNICATIONS
IED NAME: IECDevice
LD INST: LDInst
IEC/MMS TCP PORT
NUMBER:
102
INCLUDE NON-IEC
DATA: Enabled
SERVER SCANNING:
Disabled
LOCATION: LPHD DC PHV-
Nam Location
LATITUDE:
LONGITUDE:
ALTITUDE:
setting allows the user to change the TCP port number for MMS connections. The
setting,
setting, and GOOSE dataset take effect when the B30 is restarted.
LD INST
B30 Bus Differential System

IEC 61850 PROTOCOL
SERVER CONFIGURATION
Range: up to 32 alphanumeric characters
Range: up to 32 alphanumeric characters
Range: 0 to 65535 in steps of 1
Range: Disabled, Enabled
Range: Disabled, Enabled
Range: up to 80 alphanumeric characters
Range: -90.000 to 90.000 deg in steps of 0.001 deg
Range: -180.000 to 180.000 deg in steps of 0.001 deg
Range: 0 to 10,0000 m in steps of 1 m
IEC/MMS TCP PORT NUMBER
5.2 PRODUCT SETUP
is a
LOCATION
INCLUDE
setting take effect when the
5-47