B.4 MEMORY MAPPING
Table B–10: MODBUS MEMORY MAP (Sheet 32 of 61)
ADDR
REGISTER NAME
7D10
...Repeated for User Programmable Pushbutton 10
7D40
...Repeated for User Programmable Pushbutton 11
7D70
...Repeated for User Programmable Pushbutton 12
7DA0
...Repeated for User Programmable Pushbutton 13
B
7DD0
...Repeated for User Programmable Pushbutton 14
7E00
...Repeated for User Programmable Pushbutton 15
7E30
...Repeated for User Programmable Pushbutton 16
Neutral Overvoltage (Read/Write Grouped Setting) (3 modules)
7F00
Neutral Overvoltage 1 Function
7F01
Neutral Overvoltage 1 Signal Source
7F02
Neutral Overvoltage 1 Pickup
7F03
Neutral Overvoltage 1 Pickup Delay
7F04
Neutral Overvoltage 1 Reset Delay
7F05
Neutral Overvoltage 1 Block
7F07
Neutral Overvoltage 1 Target
7F08
Neutral Overvoltage 1 Events
7F09
Neutral Overvoltage 1 Curves
7F0A
Reserved (8 items)
7F11
...Repeated for Neutral Overvoltage 2
7F22
...Repeated for Neutral Overvoltage 3
Auxiliary Overvoltage (Read/Write Grouped Setting) (3 modules)
7FA0
Auxiliary Overvoltage 1 Function
7FA1
Auxiliary Overvoltage 1 Signal Source
7FA2
Auxiliary Overvoltage 1 Pickup
7FA3
Auxiliary Overvoltage 1 Pickup Delay
7FA4
Auxiliary Overvoltage 1 Reset Delay
7FA5
Auxiliary Overvoltage 1 Block
7FA7
Auxiliary Overvoltage 1 Target
7FA8
Auxiliary Overvoltage 1 Events
7FA9
Reserved (8 items)
7FB1
...Repeated for Auxiliary Overvoltage 2
7FC2
...Repeated for Auxiliary Overvoltage 3
Frequency (Read Only)
8000
Tracking Frequency
Temp Monitor Actual Values (Read Only Non-Volatile)
81C0
Reserved Register T1
81C1
Reserved Register T2
81C2
Reserved Register T3
81C4
Reserved Register T4
81C6
Reserved Register T5
81C8
Reserved Register T6
81CA
Reserved Register T7
81CC
Reserved Register T8
EGD Fast Production Status (Read Only Non-Volatile and Read Only)
83E0
EGD Fast Producer Exchange 1 Signature
83E1
EGD Fast Producer Exchange 1 Configuration
Time
83E3
EGD Fast Producer Exchange 1 Size
B-40
RANGE
0 to 1
0 to 5
0 to 3
0 to 600
0 to 600
0 to 4294967295
0 to 2
0 to 1
0 to 3
0 to 65535
0 to 1
0 to 5
0 to 3
0 to 600
0 to 600
0 to 4294967295
0 to 2
0 to 1
0 to 65535
2 to 90
-55 to 125
-55 to 125
-2147483647 to
2147483647
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 65535
0 to 4294967295
0 to 65535
B30 Bus Differential System
APPENDIX B
UNITS
STEP
FORMAT
---
1
F102
---
1
F167
pu
0.001
F001
s
0.01
F001
s
0.01
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F116
---
1
F001
---
1
F102
---
1
F167
pu
0.001
F001
s
0.01
F001
s
0.01
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F001
Hz
0.01
F001
C
1
F002
C
1
F002
---
1
F004
---
1
F003
---
1
F003
---
1
F003
---
1
F003
---
1
F003
---
1
F001
---
---
F003
---
1
F001
DEFAULT
0 (Disabled)
0 (SRC 1)
300
100
100
0
0 (Self-reset)
0 (Disabled)
0 (Definite
Time)
0
0 (Disabled)
0 (SRC 1)
300
100
100
0
0 (Self-reset)
0 (Disabled)
0
0
-55
125
0
0
0
0
0
0
0
0
0