5.5 FLEXLOGIC
Table 5–11: B30 FLEXLOGIC OPERANDS (Sheet 3 of 6)
OPERAND TYPE
OPERAND SYNTAX
ELEMENT:
Dig Element 1 PKP
Digital elements
Dig Element 1 OP
Dig Element 1 DPO
Dig Element 2 to 48
ELEMENT:
FxE 1 PKP
FlexElements
FxE 1 OP
FxE 1 DPO
FxE 2 to 8
ELEMENT:
GROUND IOC1 PKP
Ground
GROUND IOC1 OP
instantaneous
GROUND IOC1 DPO
overcurrent
GROUND IOC2 to 6
ELEMENT:
GROUND TOC1 PKP
Ground time
GROUND TOC1 OP
overcurrent
GROUND TOC1 DPO
GROUND TOC2 to 6
ELEMENT
LATCH 1 ON
Non-volatile latches
LATCH 1 OFF
LATCH 2 to 16
ELEMENT:
NEUTRAL IOC1 PKP
Neutral
NEUTRAL IOC1 OP
instantaneous
NEUTRAL IOC1 DPO
overcurrent
NEUTRAL IOC2 to 6
ELEMENT:
NEUTRAL OV1 PKP
5
Neutral overvoltage
NEUTRAL OV1 DPO
NEUTRAL OV1 OP
NEUTRAL OV2 to 3
ELEMENT:
NEUTRAL TOC1 PKP
Neutral time
NEUTRAL TOC1 OP
overcurrent
NEUTRAL TOC1 DPO
NEUTRAL TOC2 to 6
ELEMENT:
PHASE IOC1 PKP
Phase
PHASE IOC1 OP
instantaneous
PHASE IOC1 DPO
overcurrent
PHASE IOC1 PKP A
PHASE IOC1 PKP B
PHASE IOC1 PKP C
PHASE IOC1 OP A
PHASE IOC1 OP B
PHASE IOC1 OP C
PHASE IOC1 DPO A
PHASE IOC1 DPO B
PHASE IOC1 DPO C
PHASE IOC2 to 6
ELEMENT:
PHASE TOC1 PKP
Phase time
PHASE TOC1 OP
overcurrent
PHASE TOC1 DPO
PHASE TOC1 PKP A
PHASE TOC1 PKP B
PHASE TOC1 PKP C
PHASE TOC1 OP A
PHASE TOC1 OP B
PHASE TOC1 OP C
PHASE TOC1 DPO A
PHASE TOC1 DPO B
PHASE TOC1 DPO C
PHASE TOC2 to 6
5-114
OPERAND DESCRIPTION
Digital Element 1 is picked up
Digital Element 1 is operated
Digital Element 1 is dropped out
Same set of operands as shown for Dig Element 1
FlexElement 1 has picked up
FlexElement 1 has operated
FlexElement 1 has dropped out
Same set of operands as shown for FxE 1
Ground instantaneous overcurrent 1 has picked up
Ground instantaneous overcurrent 1 has operated
Ground instantaneous overcurrent 1 has dropped out
Same set of operands as shown for GROUND IOC 1
Ground time overcurrent 1 has picked up
Ground time overcurrent 1 has operated
Ground time overcurrent 1 has dropped out
Same set of operands as shown for GROUND TOC1
Non-volatile latch 1 is ON (Logic = 1)
Non-volatile latch 1 is OFF (Logic = 0)
Same set of operands as shown for LATCH 1
Neutral instantaneous overcurrent 1 has picked up
Neutral instantaneous overcurrent 1 has operated
Neutral instantaneous overcurrent 1 has dropped out
Same set of operands as shown for NEUTRAL IOC1
Neutral overvoltage element 1 has picked up
Neutral overvoltage element 1 has dropped out
Neutral overvoltage element 1 has operated
Same set of operands as shown for NEUTRAL OV1
Neutral time overcurrent 1 has picked up
Neutral time overcurrent 1 has operated
Neutral time overcurrent 1 has dropped out
Same set of operands as shown for NEUTRAL TOC1
At least one phase of phase instantaneous overcurrent 1 has picked up
At least one phase of phase instantaneous overcurrent 1 has operated
All phases of phase instantaneous overcurrent 1 have dropped out
Phase A of phase instantaneous overcurrent 1 has picked up
Phase B of phase instantaneous overcurrent 1 has picked up
Phase C of phase instantaneous overcurrent 1 has picked up
Phase A of phase instantaneous overcurrent 1 has operated
Phase B of phase instantaneous overcurrent 1 has operated
Phase C of phase instantaneous overcurrent 1 has operated
Phase A of phase instantaneous overcurrent 1 has dropped out
Phase B of phase instantaneous overcurrent 1 has dropped out
Phase C of phase instantaneous overcurrent 1 has dropped out
Same set of operands as shown for PHASE IOC1
At least one phase of phase time overcurrent 1 has picked up
At least one phase of phase time overcurrent 1 has operated
All phases of phase time overcurrent 1 have dropped out
Phase A of phase time overcurrent 1 has picked up
Phase B of phase time overcurrent 1 has picked up
Phase C of phase time overcurrent 1 has picked up
Phase A of phase time overcurrent 1 has operated
Phase B of phase time overcurrent 1 has operated
Phase C of phase time overcurrent 1 has operated
Phase A of phase time overcurrent 1 has dropped out
Phase B of phase time overcurrent 1 has dropped out
Phase C of phase time overcurrent 1 has dropped out
Same set of operands as shown for PHASE TOC1