GE B30 UR Series Instruction Manual page 284

Bus differential system
Hide thumbs Also See for B30 UR Series:
Table of Contents

Advertisement

5.6 GROUPED ELEMENTS
At 0% of pickup, the operating time equals the UNDERVOLTAGE DELAY setting.
NOTE
b) PHASE UNDERVOLTAGE (ANSI 27P, IEC PTUV)
5

PATH: SETTINGS
GROUPED ELEMENTS
 PHASE
 UNDERVOLTAGE1
Two undervoltage elements facilitate applications including undervoltage supervision of the main bus differential protection
to prevent maloperation in the event of CT trouble.
5-158
Figure 5–65: INVERSE TIME UNDERVOLTAGE CURVES
SETTING GROUP 1(6)
PHASE UV1
FUNCTION: Disabled
PHASE UV1 SIGNAL
MESSAGE
SOURCE: SRC 1
PHASE UV1 MODE:
MESSAGE
Phase to Ground
PHASE UV1
MESSAGE
PICKUP: 1.000 pu
PHASE UV1
MESSAGE
CURVE: Definite Time
PHASE UV1
MESSAGE
DELAY:
PHASE UV1 MINIMUM
MESSAGE
VOLTAGE: 0.100 pu
PHASE UV1 BLOCK:
MESSAGE
Off
PHASE UV1
MESSAGE
TARGET: Self-reset
PHASE UV1
MESSAGE
EVENTS: Disabled
B30 Bus Differential System
% of voltage pickup
842788A1.CDR

VOLTAGE ELEMENTS
Range: Disabled, Enabled
Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
Range: Phase to Ground, Phase to Phase
Range: 0.000 to 3.000 pu in steps of 0.001
Range: Definite Time, Inverse Time
Range: 0.00 to 600.00 s in steps of 0.01
1.00 s
Range: 0.000 to 3.000 pu in steps of 0.001
Range: FlexLogic operand
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
5 SETTINGS
PHASE UNDERVOLTAGE1(3)
GE Multilin