Check item after completing the installation
f Before supplying the power, use DC 500V insulation resistance tester to measure the power (L, N) terminal and the
f
outdoor unit grounding. Measurement should be over 30MΩ.
• Since you may damage the communication circuit if you test the communication terminal, do not test it.
• Use common circuit tester on communication terminal for open/short circuit.
CAUTION
Trial operation and switch operation specification
1. Check the power between the outdoor unit and the cabinet panel.
- Single phase power supply L, N
- 3 phase power supply: R, S, T, N
2. Check the indoor unit.
1) Check for proper connection of the power and communication cable for each indoor units. (Communication cable
for indoor and outdoor unit is F1, F2)
2) Check for proper connection of the connection terminal such as temperature sensor, drain pump and display etc.
3. Press the [K1] or [K2] button on the outdoor unit PCB to start and stop the trial operation mode..
- Pressing [K1] button 1 time  Start Heating trial operation  Pressing [K1] button  Stop  Display 7-Seg for Heating
trial mode:
- Pressing [K2] button 1 time  Start Cooling trial operation  Pressing [K2] button  Stop  Display 7-Seg for Cooling
trial mode:
- Pressing [K1] button 2 time  Start Defrost trial operation  Pressing [K1] button  Stop  Display 7-Seg for Defrost
trial mode:
Condition 1: Outdoor temperature below 10°C
Condition 2: All temperature condition must meet the defrost condition
Mirage_AP36M0@_IBIM_E_34573A(1).indd 47
SEG1
D
E
F
Main MICOM version
Year (Hex)
Inverter MICOM version
Year (Hex)
E2P version
Year (Hex)
SEG2
SEG3
Protection control
0: No protection
control
1: Frozen
0: Cooling
2: Non-stop defrost
1: Heating
3: Overload
4: Discharge
5: Full current
100 unit
10 unit
-
-
Month (Hex)
Month (Hex)
Month (Hex)
SEG4
Unit
Frequency status
0: Normal
1: Hold
-
2: Down
3: Up_limit
4: Down_limit
Single unit
-
-
-
Day (10 unit)
Day (single unit)
Day (10 unit)
Day (single unit)
Day (10 unit)
Day (single unit)
2012-02-21 오후 1:09:59
47

Advertisement

Table of Contents
loading

Table of Contents