Record Number - Maximum number of records is 255.
System Input Type
System Output Type
Input Voltage
Output Voltage
Output Load
DC Input Voltage
Battery Voltage
Slot Location
Fault
4200FA/4300 Fault Records Log Format
Log Date – This field shows the date of the recording.
Log Time - This field shows the time that the values were recorded. Time is displayed in the hh:mm:ss 24-
hour format (i.e., 8:30 p.m. is 20:30:00).
Record Number – Maximuan number of record is 255.
Fault 1 – Description of fault detected.
Fault 2 – Description of fault detected.
Following is a table of the possible UPS fault codes and their meanings. Please refer to UPS manual for more specific
details.
Fault Code
FSOPEN
CL
DCOC
DCOV
DCIB
VOUV
VOOV
DVCOH
BYPOL
CHRGOV
OOC
DCUVBS
DCUVC
BYPOH
INVOLRSTAOK
INVOLRSTNOK
OH
DCUB
OL
PHIRER
PHBRER
EPO
Operation Mode Records
86
Description
Fuse opened
Current limit fault occurred
DC bus over current fault occurred
DC bus over voltage occurred
DC bus imbalance occurred
Output voltage undervoltage occurred
Output voltage overvoltage occurred
Device overheat occurred
Bypass overload occurred
Charger overvoltage occurred
Output overcurrent occurred
DC bus under voltage occurred at boostup UPS state
DC bus under voltage occurred at charging of UPS state
Bypass overheat occurred
Inverter overload occurred and it is resettable
Inverter overload occurred and it is NOT resettable
UPS Overheat
DC Imbalance
UPS Overlaod
Phase Error
Bypass Phase Error
Emergency Power Off
Table 2: UPS Fault Codes