UPS Restart After Battery Shutdown Enable
This field shows the present mode set for UPS input power detection immediately after a shutdown while on
batteries. It is set by the administrator.
0 – Disable
1 – Enable
Default Value = Enable
UPS Restart After Battery Shutdown Delay (secs)
This field shows the time delay, in seconds, before UPS Start Up immediately following a shutdown while on
batteries. It is set by the administrator.
Range – 0 to 800 seconds: UPS Restart After Battery Shutdown Enable must be Enabled in order to function.
Default Value = 10
UPS Restart Mode
This field shows the mode at which to enter when UPS is restarted. It can either enter Bypass state or On-Line state.
It is set by the administrator.
0- Bypass: UPS Restart After Battery Shutdown Enable must be Enabled in order to function.
1- On-Line
Default Value = On-Line
UPS Auto Transfer Enable
This field shows the present mode for the auto transfer of the UPS. This allows the UPS to transfer from On-Line to
Bypass or vise-versa. It can be enabled or disabled. It is set by the administrator.
0 – Disable
1 – Enable
Default Value = Enable
UPS Auto Retransfer Delay (secs)
This field shows the time period to wait after fault occurrence before attempting transfer back On-Line. It is set by the
administrator.
Range – 0 to 600 seconds: UPS Auto Transfer Enable must be Enabled in order to function.
Default Value = 3
Remote Contact Shutdown State
This field shows the present state of the remote contacts shutdown control. It can be open or closed.
0 – Open (Software Defined)
Invert Remote Contact Shutdown Logic
This field shows the logic state of the remote contact shutdown. It can be non-inverted or inverted. It is set by the
administrator.
0 – Not Inverted
1 – Inverted
Default Value = Not Inverted
Remote Contact Shutdown Mode Selection
This field shows the mode of the remote contact shutdown. It is set by the administrator.
0 – Bypass
1 – Shutdown while contact closed
Default Value = Bypass
RemotEye III User Manual – 62330-005