8 Maintenance and fault rectification
Fault messages via the
indicating/adjustment
module
Reaction after fault rec-
tification
44
? 4 ... 20 mA signal missing
Wrong connection
l
à Check connection according to chapter "Connection
steps" and if necessary, correct according to chapter
"Wiring plan"
No power supply
l
à Check cables for breaks; repair if necessary
supply voltage too low or load resistance too high
l
à Check, adapt if necessary
? Current signal greater than 22 mA or less than 3.6 mA
Electronics module defective
l
à Exchange instrument or return instrument for repair
In Ex applications, the regulations for the wiring of intrinsically
safe circuits must be observed.
? E013
no measured value available
l
à sensor in boot phase
à Sensor does not find an echo, e.g. due to faulty
installation or wrong parameter adjustment
? E017
Adjustment span too small
l
à Carry out a fresh adjustment and increase the distance
between min. and max. adjustment
? E036
no operable sensor software
l
à Carry out a software update or send the instrument for
repair
? E041, E042, E043
Hardware error, electronics defective
l
à Exchange instrument or return instrument for repair
Depending on the failure reason and measures taken, the
steps described in chapter "Set up" must be carried out again,
if necessary.