Vega VEGAPULS 63 Operating Instructions Manual page 35

Radar sensor for continuous level measurement of aggressive liquids or with hygienic requirements 20 ma/hart - four-wire
Hide thumbs Also See for VEGAPULS 63:
Table of Contents

Advertisement

Reset
VEGAPULS 63 • 4 ... 20 mA/HART - four-wire
6 Set up with the indicating and adjustment module PLICSCOM
Current output
l
Unit of measurement
l
Language
l
The following safety-relevant data are not read out or written:
HART mode
l
PIN
l
SIL
l
Copy sensor data
Copy sensor data?
Basic adjustment
If the "Reset" is carried out, the sensor resets the values of the
following menu items to the reset values (see chart):
Menu item
Max. adjustment
Min. adjustment
Medium
Vessel form
Damping
Linearisation
Sensor-TAG
Displayed value
Extended settings
Current output - characteristics
Current output - max. current
Current output - min. current
Current output - failure
Unit of measurement
The values of the following menu items are not reset to the
reset values (see chart) with "Reset":
Menu item
Lighting
Language
SIL
Sensor-specific basic adjustment.
2)
Reset value
0 m(d)
30 m(d) (VEGAPULS 61, 63, 65, 67)
35 m(d) (VEGAPULS 62, 66)
70 m(d) (VEGAPULS 68)
Liquid
not known
0 s
linear
Sensor
Distance
None
4 ... 20 mA
20 mA
4 mA
< 3.6 mA
m(d)
Reset value
no reset
no reset
no reset
2)
35