Sensor orientation
Vessel installations
Agitators
VEGAPULS 63 • 4 ... 20 mA/HART - four-wire
Align the sensor in liquids as vertical as possible to the product
surface to achieve optimum measurement.
Fig. 8: Alignment in liquids
The mounting location of the radar sensor should be a place
where no other equipment or fixtures cross the path of the
microwave signals.
Vessel installations such as, for example, ladders, limit
switches, heating spirals, struts, etc. can cause false echoes
that get superimposed on the useful echo. Make sure when
planning your measuring site that the radar sensor has a "clear
view" to the measured product.
In case of existing vessel installations, a false echo storage
should be carried out during setup.
If large vessel installations such as struts or supports cause
false echoes, these can be attenuated through supplementary
measures. Small, inclined sheet metal baffles above the
installations scatter the radar signals and prevent direct
interfering reflections.
Fig. 9: Cover smooth profiles with deflectors
If there are agitators in the vessel, a false echo storage should
be carried out with the agitators in motion. This ensures that
the interfering reflections from the agitators are saved with the
blades in different positions.
4 Mounting
17