Vega VEGAPULS 63 Operating Instructions Manual page 19

Radar sensor for continuous level measurement of aggressive liquids or with hygienic requirements 20 ma/hart - four-wire
Hide thumbs Also See for VEGAPULS 63:
Table of Contents

Advertisement

VEGAPULS 63 • 4 ... 20 mA/HART - four-wire
Fig. 11: Pipe antenna system in a tank. The vent hole in the surge pipe must be
in one plane with the polarisation marking on the sensor.
1
Marking of the polarisation direction
2
Vent holde max. ø 5 mm (0.2 in)
If possible, the antenna diameter of the sensor should
correspond to the inner diameter of the tube. With VEGAPULS
63 this is approx. 40 mm (1.575 in). The sensor can be used
with tube diameters between 40 ... 80 mm (1.575 ... 3.15 in).
Bypass tube
As an alternative to the surge pipe in the vessel, a pipe system
can be mounted outside of the vessel as a bypass tube. For
setup, select the function "Bypass tube".
Align the sensor in such a way that the polarisation marking on
the process fitting is in the same plane as the tube holes or the
tube connection openings (see illustration: "VEGAPULS in a
bypass tube").
max.
1
2
min.
4 Mounting
19