Plotarea (Zoom) - JUMO LOGOLINE 500d Operating Manual

Pen recorder with text printing and led dot matrix display
Table of Contents

Advertisement

8.4.6 Plotarea (zoom)

Defines the range of the input signal to be
recorded on the chart. The complete range
or an enlarged section can be recorded. In-
put is in percent. The low value designates
the point of the measurement range which
becomes the new zero. The high value des-
ignates the new end value.
measurement range (scaling start to scaling
end) corresponds to 100%.
The difference between low and
high value must be at least 10%.
The low value is calculated as follows:
(smallest value to be recorded – start of scaling) /
(end of scaling – start of scaling) h 100%
The high value is calculated as follows:
(largest value to be recorded – start of scaling) /
(end of scaling – start of scaling) h 100%
Display
PLOTAREA
8 Programming
The entire
Edit
Selection/input
E
2 PLOTAREA
Select recording channel
2 LOW: 010 %
2
Input start of
presentation range of
measurement value
(in percent of the
measurement range)
2 HIGH: 100 %
3
Input end of presentation
range of measurement
value (in percent of the
measurement range)
with keys Enter
h
R
,
h
R
,
,
l
r
,
h
R
,
,
l
r
,
76
Continue with
E
2
E
3
Check:
0
start
90%
E
h
forwards
R
backwards
Check:
end
100%
and end–start
10%