8.4.3 Scaling

The scaling start/end value and the dimen-
sion (unit) are defined to record the meas-
urement. For the alpha-numerical presenta-
tion of the measurement on the display and
on the chart, the number format is selected.
Section 7.4
Example:
A temperature transmitter supplies a voltage
within the range of 0 — 10V. This range cor-
responds to a temperature of 200 — 600°C.
Programming:
Unit:
Scaling start:
Scaling end:
Number format:
Display
SCALING
8 Programming
°C
200
600
XXX.X
Edit
Selection/input
E
3 SCALING
Select recording channel
3 DIMENSION: _ _ _ _
2
5 digits freely selectable
3 ZERO
3
+200.0 °C
Input start of scaling
3 FULL
4
+600.0 °C
Input end of scaling
3 DECIMAL POINT:
5
x.xxx
Select decimal place :
AUTO, x.xxx, xx.xx, xxx.x,
xxxx.
with keys Enter
h
R
,
h
R
,
,
S
h
R
,
,
l
r
,
,
S
h
R
,
,
l
r
,
,
S
h
R
,
73
Continue with
E
2
E
3
E
4
E
5
Check
<>
zero
full
E
h
forwards
R
backwards

Advertisement

Table of Contents
loading