Powerware
9 Prestige Series User's Guide (3000 VA)
®
11. See the following table for specifications and tightening torque.
Power Cable Terminations
Wire Function
Terminal
Position
Ground
1, 8
Input/Output
2, 3 and 5, 6
No Connection
4, 7
*
Use #10-AWG 75
C copper wire. Maximum ambient temperature 40
12. Replace the terminal box cover.
13. Remove the battery connector guard. Plug the battery cord into
the external battery connector on the UPS. All battery
connectors are polarized to prevent incorrect connection.
14. If additional battery cabinets are to be used, plug the battery
cord of the second cabinet into the external battery connector
of the first battery cabinet. Follow this procedure for each
additional battery cabinet.
15. Remove the breaker tie from the circuit breaker on all battery
cabinets.
16. Switch the circuit breaker on all battery cabinets to the ON (
position.
17. Start the UPS according to the following "UPS with PPDM
Startup" procedure.
:
www.powerware.com
Tightening Torque
Terminal Wire
Entrelec
Size Rating*
10 AWG
7.1 - 8.9 lb in
2
(2.5 mm
)
10 AWG
3.5 - 5.3 lb in
2
(2.5 mm
)
Installation
Phoenix
Contact
11 - 15 lb in
5 - 7 lb in
C.
)
|
37