3 x 100 WATTS x 1.4 = 420 VA
If the total load requirements of the equipment exceeds the capacity of
the UPS, you must either reduce the number of pieces of equipment, or
use a UPS with a larger load capacity.
When deciding on which pieces of equipment to remove from the UPS,
select equipment that has a lower priority for power protection.
Computers, monitors, and modems typically have a higher priority
because they could be processing or transmitting data when a power
outage occurs.

Battery Times for the Prestige 3000

During a power failure, the UPS battery supplies power to your
equipment, providing time to complete computing activities prior to
UPS shutdown. The duration of this time period is directly related to the
UPS battery configuration. By adding battery cabinets, you can
customize the UPS to provide enough battery time for normal processing
activities.
*
Powerware
9 Prestige Series User's Guide (3000 VA)
®
3 COMPUTERS
100 WATTS
EACH
420 VA + 720 VA + 50 VA = 1190 VA (Total Load Requirements)
Figure 2. Volt-Amperes Calculation Example
Load (VA)
Load (VA)
Load (W)
Load (W)
at .7 PF*
400
280
800
560
1200
840
1600
1120
2000
1400
2500
1750
3000
2100
Typical Power Factor (PF)
:
www.powerware.com
3 MONITORS
2 AMPS
EACH
3 x 2 AMPS x 120 = 720 VA
Approximate Battery Time (in Minutes)
1 Cabinet
2 Cabinets
72
150
36
23
16
12
8
6.5
Introduction
EXTERNAL
MODEM
50 VA
50 VA
3 Cabinets
227
79
122
53
82
38
61
30
48
23
37
17
29
3