Powerware 9 Prestige Series User Manual page 39

3000 va; 120v
Hide thumbs Also See for 9 Prestige Series:
Table of Contents

Advertisement

Power Input
Connector
(L5-30P)
Input
Breaker
(30A)
UPS Cabinet
Battery
Circuit
Breaker
Breaker Tie
Battery
Cabinet
Powerware
9 Prestige Series User's Guide (3000 VA)
®
Figure 4. UPS Rear Panel
4. If additional battery cabinets are to be used, plug the battery
cord of the second cabinet into the external battery connector
of the first battery cabinet. Follow this procedure for each
additional battery cabinet.
5. Remove the breaker tie from the circuit breaker on all battery
cabinets.
6. Switch the circuit breaker on all battery cabinets to the ON (
position.
7. The equipment to be protected by the UPS should be powered
off. Plug the equipment into the power output receptacles on
the UPS rear panel.
DO NOT protect laser printers with the UPS because of the
exceptionally high power requirements of the heating elements.
8. Verify that the load plug is fully seated.
9. Start the UPS according to the following "UPS Startup"
procedure.
: