Configuration Procedure; Table 3-3 Configuration Procedure - Honeywell UDC2500 Product Manual

Universal digital controller
Hide thumbs Also See for UDC2500:
Table of Contents

Advertisement

Configuration

3.3 Configuration Procedure

Introduction
Each of the Set Up groups and their functions are pre-configured at the factory.
The factory settings are shown in Section 3.11.
If you want to change any of these selections or values, follow the procedure in Table
3-3. This procedure tells you the keys to press to get to any Set Up group and any
associated Function parameter prompt.
Procedure
ATTENTION
The prompting scrolls at a rate of 2/3 seconds when the SET UP or FUNCTION key is held in.
Also,
or
Step
Operation
1
Enter Set Up
Mode
2
Select any Set
Up Group
3
Select a Function
Parameter
Change the
4
Value or
Selection
5
Enter the Value
or Selection
Exit Configuration
6
keys will move group prompts forward or backward at a rate twice as fast.

Table 3-3 Configuration Procedure

Press
Upper Display = SET
SET UP
Lower Display = LOCK (This is the first Set Up Group title)
Sequentially displays the other Set Up group titles shown in
SET UP
the prompt hierarchy in Table 3-2 Configuration Prompt
Hierarchy.
You can also use the
groups in both directions. Stop at the Set Up group title that
describes the group of parameters you want to configure.
Then proceed to the next step.
Upper Display = the current value or selection for the first
FUNCTION
Lower Display = the first Function prompt within that Set Up
Sequentially displays the other function prompts of the Set
Up group you have selected. Stop at the function prompt
that you want to change, then proceed to the next step.
Increments or decrements the value or selection that
or
appears for the selected function prompt. If you change the
value or selection of a parameter while in Set Up mode then
decide not to enter it, press [MAN-AUTO/RESET] once—the
original value or selection is recalled.
Enters value or selection made into memory after another
FUNCTION
key is pressed.
Exits configuration mode and returns controller to the same
LOWER
state it was in immediately preceding entry into the Set Up
DISPLAY
mode. It stores any changes you have made.
If you do not press any keys for 30 seconds, the controller
times out and reverts to the mode and display used prior to
entry into Set Up mode.
UDC2500 Universal Digital Limit ControllerProduct Manual
Result
or
keys to scan the Set Up
function prompt of the selected Set Up
group.
group.
30

Advertisement

Table of Contents
loading

Table of Contents