Open collector outputs are internally powered at +30 Vdc. Connecting an external
CAUTION
1
power supply will damage the controller.
2
Electromechanical relays are rated at 5 Amps @120 Vac or 30 Vdc and 2.5 Amps at 240 Vac.
Customer should size fuses accordingly. Use Fast Blo fuses only.
16 SHLD
17 D+ (B)
18 D– (A)
1 Do not run the communications lines in the same conduit as AC power.
2 Use shielded twisted pair cables (Belden 9271 Twinax or equivalent).

Figure 2-10 RS-422/485 Communications Option Connections

Time Simplex
Relay Load
To terminal
4 or 6
Relay Load
To terminal
7 or 9

Figure 2-9 Open Collector Output

1
SHLD
D+
D–
TO OTHER
COMMUNICATION
CONTROLLERS
D–
120 OHMS ON LAST LEG
UDC2500 Universal Digital Limit ControllerProduct Manual