EPD, EPPD
Electrical Wiring – Three Phase
WARNING
Check that the power is locked off and disconnected before working on
pump. All electric work should be performed by a qualified electrician and all
national and local electrical codes must be observed.
(1) Wiring
a) Wire as indicated for the appropriate start system as shown in Fig. 4
b) Loose connections will stop the pump. Make sure all electrical connections are secure.
MOTOR WIRING DIAGRAM
• Model P707U
• Output
1
/
to 1
1
/
2
2
(BLACK)
(RED)
(WHITE)
(GREEN/YELLOW)
Fig. 4
Use with approved motor control that matches motor input in full load amperes with overload
element(s) selected or adjusted in accordance with control instructions.
Utiliser un d é marreur approuv é convenant au courant á pleine charge du moteur et dont les
é l é ments thermiques sont r é gl é s ou choisis conform é ment aux instructions qui l'accompagnent.
(2) Cable
a) Never let the end of the cable contact water.
b) If the cable is extended, do not immerse the splice in water.
c) Fasten the cable to the discharge piping with tape or vinyl strips.
d) Install the cable so that it will not overheat. Overheating is caused by coiling the
cable and exposing it to direct sunlight.
(3) Grounding
As shown in Fig. 5 ground the green/yellow wire (label E). Under no circumstances
should the green/yellow wire be connected to the power supply.
(4) Use short circuit breakers to prevent danger of electrical shock.
OPERATION
1. Before starting the pump:
(1) After completing installation, measure the insulation resistance again as described in
INSTALLATION.
(2) Check water level.
If the pump is operated continuously for an extended period of time in a dry condition
or at the lowest water level, the motor protector will be activated in single phase units.
Constant repetition of this action will shorten pump service life. Do not start the pump
again in such a situation until after the motor has completely cooled.
CALL 1-800-577-8111 FOR SALES AND SUPPORT
HP
NOTE:
U phase: black
V phase: red
W phase: white
E phase: green/yellow
ground
plate
* Three phase only
Fig. 5