Transistor output
Item
No. of output points
Connection type
Output type
External power supply
Max. load
Open circuit leakage current
Voltage drop when ON
Response time
Output circuit insulation
Indication of output operation
Output circuit configuration
2.5
Input/Output Derating Curve
The derating curve below shows the simultaneous ON ratio of available PLC inputs or outputs with respect to the ambient
temperature. Use the PLC within the simultaneous input or output ON ratio range shown in the figure.
Derating curve
When 24 V DC service power supply or external power supply (24 V DC) is used for input circuits
FX5UJ-MR/ES
Simultaneous ON ratio
100%
80%
55%
50%
0
C
35
2 SPECIFICATIONS
32
2.5 Input/Output Derating Curve
Output specifications
FX5UJ-24MT/
10 points
FX5UJ-40MT/
16 points
FX5UJ-60MT/
24 points
Removable terminal block (M3 screws)
FX5UJ-MT/ES
Transistor/sink output
FX5UJ-MT/ESS
Transistor/source output
5-30 V DC
0.5 A/point
The total load current per common terminal should be the following value.
• 3 output points/common terminal: 0.6 A or less
• 4 output points/common terminal: 0.8 A or less
For details on the common, refer to Page 37 Interpretation of terminal block layout.
0.1 mA or less/30 V DC
Y0 to Y2
1.0 V or less
Y3 and subsequent
1.5 V or less
Y0 to Y2
2.5 μs or less/10 mA or more (5-24 V DC)
Y3 and subsequent
0.2 ms or less/200 mA or more (24 V DC)
Photo-coupler insulation
LED is lit when output is on
Sink output wiring
DC power supply
A number is entered in the of [COM ].
When output load is 1A
When output load is 2A
C
40
C 47
C
55
C
Ambient temperature
Load
Y
COM
Fuse
FX5UJ-MT/
Simultaneous ON ratio
100%
55%
0
C
Source output wiring
Load
Y
DC power supply
+V
Fuse
A number is entered in the of [+V ].
50
C
55
C
Ambient temperature