Strata CTX Configuration

Primary/Reserve Power Cabinet Hardware

Table 1-63
Battery Charger Characteristics
Charger: current limiting
Nominal float voltage: 2.275 volts/cell
Charge current: 0.7 amps maximum
Battery discharge cut-off voltage: 20.5
Table 1-64
CTX670 Typical Reserve Power Duration Estimates
Number of Cabinets
Estimated operation time
Two-battery configuration
Estimated operation time
Four-battery configuration
DC Current Drain
(-24VDC)
1. Assumes 80 ampere-hours with 12VDC batteries.
Primary/Reserve Power Cabinet Hardware
The type of cabinet mounting can have an effect the power requirements. There are two types of
mounting for the CTX100 and CTX670 (listed below).
• Cabinet Wall Mounting – The lightweight and compact design of CTX100 and CTX670
enables easy wall mounting. Wall Mounting requires no special hardware.
• Cabinet Floor Mounting – Only the CTX670 can be floor mounted (requires the BFIF
hardware kit). If floor mounting three or more cabinets, AC and reserve power must be
connected to the BCCB conduit connection box option by a licensed electrician. If more than
two cabinets require reserve power batteries, the BBDB must be installed.
Underwriters' Laboratory (UL) and local electrical codes require certain standards for connecting
commercial AC and reserve power to the Strata CTX system.
assemblies may be required to meet UL and local electrical code standards.
The power distribution hardware for the CTX100 is shown in
Table 1-65
CTX100 Cabinet Power Distribution Hardware
Option
APSU112
ABTC-3M
ABCS
1-48
CTX670 Reserve Power Characteristics
±
0.5VDC
1
12.0 hr.
6.0 hr.
24.0 hr.
12.0 hr.
4.6 amps.
8.7 amps.
Strata CTX100 cabinet power supply is supplied with each cabinet. Operates with 120VAC as
the system's primary power source and requires 1.8 amps AC per cabinet.
The power supply AC cord is 5 ft. long with a standard three prong plug.
A three-meter long battery cable is used to connect reserve power batteries to the ABCS battery
charger when the system has less than three cabinets. One reserve power cable is required for
each cabinet.
Option battery charger that is installed on the APSU112 power supply. One per cabinet is
required with the ABTC-3M if connecting reserve power batteries to the CTX100.
Maximum Battery Charger Drain (-24VDC)
1 cabinet
6.0 amps
2 cabinets
12.0 amps
3 cabinets
18.0 amps
4 cabinets
24.0 amps
1
2
3
4
4.0 hr.
3.0 hr.
8.0 hr.
6.0 hr.
12.8
16.9
amps.
amps.
Description
5 cabinets
30.0 amps
6 cabinets
36.0 amps
7 cabinets
42.0 amps
5
6
2.5 hr.
2.0 hr.
5.0 hr.
4.0 hr.
21.0
25.1
amps.
amps.
Tables 1-63
and
1-66
describe which
Table
1-65.
Strata CTX I&M
7
1.8 hr.
3.5 hr.
29.2
amps.
10/02