6
Only with rematic
SR 5240 C1 or 2945
C3 K control: Check
the communication
between control and
boiler by means of
the two LED's on
the interface, visible
through the transpa-
rant part of the control
panel.
00W4H7900019
7
Investigate boiler set-
tings and wiring
Table 17 Fault-finding
10.2 Fault codes
In the event of an error message, both the 'code'-display and the t-display will flash.
For details, see Table 18.
For a readout of the most recent faults, see Par. 6.9.
IMPORTANT:
Before resetting, accurately record the fault code (including figures, flashing digits and
dots) and remember to pass on this information when seeking assistance. The fault
code is important for correctly and rapidly tracing the nature of the fault.
NOTE: Shut-off mode (code b, only dots in t-display are flashing, not digits) is a
normal boiler operating function and does not represent a boiler failure. However, this
may indicate a system problem, an internal fan check or an incorrect parameter
setting.
57117.indd 53
57117.indd 53
LED 1 is not flashing?
®
LED 2 is not flashing?
Both LED's are flashing?
Check the wiring on the
terminal strip and on the
control box
Check the parameter set-
tings of the boiler
Check the wiring on the
boiler terminal strip and to
the Gasmodul control box
53
Interface or control box
is faulty
Interface or control is
faulty
If the wiring is correct,
replace the control box.
If all is correct, replace
the control box.