REMEHA Quinta 30 Technical Information page 23

High-effi ciency condensing boiler
Table of Contents

Advertisement

- While holding both keys pressed, set the t-display to 12, using the [+] or [-]-
keys and press the 'e'-key.
- The display will flash twice confirming acceptance of the access code.
- Release the keys and c12 will dissappear from the display. You are now in the
service mode
WARNING: changing factory defaults without reference to the tables contained in this
manual may result in incorrect operation.
- To delete the service code press the 'reset'-key once
- If no keys are pressed over a 15 minute period the service code will delete automa-
tically
Code Description
Flow temperature set point during
$
forced part load
High limit temperature set point
%
Fan speed at full load (HTG)
^
Fan speed at part load (HTG and
&
DHW)
Modulation start point ΔT (F/R)
*
Interface selection (control option) 00 internal (Chronotherm
(
DHW cut-in ΔT
B
Fan speed at full load (DHW)
C
Intern
D
N/a
E
N/a
F
Forced part load time after start
G
(HTG)
Fan speed at start
H
57117.indd 23
57117.indd 23
Setting range
20 - 90ºC
90 – !0 (= 110°C)
10 – 60 hundreds
10 – 60 hundreds
05 - 30 ºC
control only)
01 external interface
10 – 05 read 1 - 5 °C
06 read 10 °C
07 read 15 °C
08 read 20 °C
10 – 60 hundreds
May not be changed!
00 – 15 minutes
May not be changed!
23
Preset
Q30
80
)0 (=100)*
48
12
25
01
05
48
00
)0 (=100)*
25
03
25