Fig. 05
Minimum clearances around the boiler
05.W3H.79.00065
7.3 Flue gas discharge and air supply
7.3.1 General
The Remeha Quinta 30 is suitable for conventional room ventilated or room sealed
operation. Specify at the time of ordering if the boiler is to be installed for twin pipe
room sealed operation. In that case, the boiler will be supplied with an adaptor plate
(concentric to twin pipe).
Before installing flue system, remove the transit cover plate.
Fig. 06
Top view Remeha Quinta (standard concentric version with optional twin
pipe adaptor shown right)
05. W3H.79.00077 + 00.W3H.79.00045
57117.indd 30
57117.indd 30
Remeha Quinta 30
The following minimum clearances are
required:
- Front: 600 mm
- Sides: 25 mm
- Bottom: 250 mm
- Top: 400 mm.