7.3.4 Single boiler conventional flue

Fig. 07
Flue gas discharge duct without bends, single boiler, conventional flue.
04.W3H.79.00004
max eq. Length L
eq. Length bend 45°
eq. Length bend 90°
Table 13 Calculation data conventional flue
Example: Quinta 30, total length 15 m, 2 bends 90°.
15 m + 2 x 4 = 23 < 40: flue OK.
Note: If the design parameters are outside the values shown in the above table or
there is any doubt over the flue system, please contact our technical department for
calculation to be undertaken.
57117.indd 33
57117.indd 33
Quinta 30
80 mm
m
40
m
1.2
m
4
33
1-4-2009 14:35:52
1-4-2009 14:35:52