1.4540.018 – Coil Current Fail High
Red alarm. Initiated by TecJet.
Cause
Hardware not ready for operation.
1.4540.019 – Position Fail High
Red alarm. Initiated by TecJet.
Cause
Hardware not ready for operation.
1.4540.020 – Elec Temp Fail Low
Red alarm. Initiated by TecJet.
Cause
Hardware not ready for operation.
1.4540.021 – FGT Fail Low
Red alarm. Initiated by TecJet.
Cause
Gas temperature before TecJet is
below the preset limit value.
1.4540.022 – Delta P Fail Low
Red alarm. Initiated by TecJet.
Cause
Delta-p from TecJet below the set
limit value.
1.4540.023 – FGP Fail Low
Red alarm. Initiated by TecJet.
Cause
Gas pressure before TecJet is
below the preset limit value.
1.4540.024 – Coil Current Fail Low
Red alarm. Initiated by TecJet.
Cause
Hardware not ready for operation.
88 | Troubleshooting | MS150122/00E 2015-07
Corrective action
u Restart TecJet.
Corrective action
u Restart TecJet.
Corrective action
u Restart TecJet.
Corrective action
u Check TecJet and configuration.
Corrective action
u Check TecJet and configuration.
Corrective action
u Check TecJet and configuration.
Corrective action
u Restart TecJet.