1.4540.011 – Flow Not Reached
Red alarm. Initiated by TecJet.
Cause
No gas flow detected.
1.4540.012 – Valve Position Error
Red alarm. Initiated by TecJet.
Cause
Hardware not ready for operation.
1.4540.013 – High Elec Temp
Red alarm. Initiated by TecJet.
Cause
Hardware not ready for operation.
1.4540.014 – Elec Temp Fail High
Red alarm. Initiated by TecJet.
Cause
Hardware not ready for operation.
1.4540.015 – FGT Fail High
Red alarm. Initiated by TecJet.
Cause
Hardware not ready for operation.
1.4540.016 – Delta P Fail High
Red alarm. Initiated by TecJet.
Cause
Differential pressure at TecJet too
high.
1.4540.017 – FGP Fail High
Red alarm. Initiated by TecJet.
Cause
Hardware not ready for operation.
Corrective action
1. Check inlet and outlet.
2. Check gas pressure, gas quality, gas filter, gas line for obstruction.
3. Check engine for overloading.
Corrective action
u Restart TecJet.
Corrective action
u Restart TecJet.
Corrective action
u Restart TecJet.
Corrective action
u Restart TecJet.
Corrective action
1. Check gas pressure.
2. Check TecJet for dirt.
Corrective action
u Restart TecJet.
MS150122/00E 2015-07 | Troubleshooting | 87