MTU 20V4000Lx2x Operating Instructions Manual page 58

Table of Contents

Advertisement

112314 – HI T-Exhaust B4
Yellow alarm. Initiated by EMU.
Cause
Individual exhaust gas
temperature of this cylinder is too
high in comparison with weighted
average.
112315 – HI T-Exhaust B5
Yellow alarm. Initiated by EMU.
Cause
Individual exhaust gas
temperature of this cylinder is too
high in comparison with weighted
average.
112316 – HI T-Exhaust B6
Yellow alarm. Initiated by EMU.
Cause
Individual exhaust gas
temperature of this cylinder is too
high in comparison with weighted
average.
112317 – HI T-Exhaust B7
Yellow alarm. Initiated by EMU.
Cause
Individual exhaust gas
temperature of this cylinder is too
high in comparison with weighted
average.
112318 – HI T-Exhaust B8
Yellow alarm. Initiated by EMU.
Cause
Individual exhaust gas
temperature of this cylinder is too
high in comparison with weighted
average.
58 | Troubleshooting | MS150122/00E 2015-07
Corrective action
1. Check emission values.
2. Check ignition timing (→ Page 143).
3. Check valve drive (exhaust valves do not close).
Corrective action
1. Check emission values.
2. Check ignition timing (→ Page 143).
3. Check valve drive (exhaust valves do not close).
Corrective action
1. Check emission values.
2. Check ignition timing (→ Page 143).
3. Check valve drive (exhaust valves do not close).
Corrective action
1. Check emission values.
2. Check ignition timing (→ Page 143).
3. Check valve drive (exhaust valves do not close).
Corrective action
1. Check emission values.
2. Check ignition timing (→ Page 143).
3. Check valve drive (exhaust valves do not close).