112504 – HIHI T-Exhaust A4
Red alarm. Initiated by EMU.
Cause
Individual exhaust gas
temperature of this cylinder is too
high in comparison with weighted
average.
112505 – HIHI T-Exhaust A5
Red alarm. Initiated by EMU.
Cause
Individual exhaust gas
temperature of this cylinder is too
high in comparison with weighted
average.
112506 – HIHI T-Exhaust A6
Red alarm. Initiated by EMU.
Cause
Individual exhaust gas
temperature of this cylinder is too
high in comparison with weighted
average.
112507 – HIHI T-Exhaust A7
Red alarm. Initiated by EMU.
Cause
Individual exhaust gas
temperature of this cylinder is too
high in comparison with weighted
average.
112508 – HIHI T-Exhaust A8
Red alarm. Initiated by EMU.
Cause
Individual exhaust gas
temperature of this cylinder is too
high in comparison with weighted
average.
64 | Troubleshooting | MS150122/00E 2015-07
Corrective action
1. Check emission values.
2. Check ignition timing (→ Page 143).
3. Check valve drive (exhaust valves do not close).
Corrective action
1. Check emission values.
2. Check ignition timing (→ Page 143).
3. Check valve drive (exhaust valves do not close).
Corrective action
1. Check emission values.
2. Check ignition timing (→ Page 143).
3. Check valve drive (exhaust valves do not close).
Corrective action
1. Check emission values.
2. Check ignition timing (→ Page 143).
3. Check valve drive (exhaust valves do not close).
Corrective action
1. Check emission values.
2. Check ignition timing (→ Page 143).
3. Check valve drive (exhaust valves do not close).