MTU 20V4000Lx2x Operating Instructions Manual page 72

Table of Contents

Advertisement

112705 – HIHI T-Exhaust A5 (abs)
Red alarm. Initiated by EMU.
Cause
Individual exhaust gas
temperature of this cylinder is too
high.
112706 – HIHI T-Exhaust A6 (abs)
Red alarm. Initiated by EMU.
Cause
Individual exhaust gas
temperature of this cylinder is too
high.
112707 – HIHI T-Exhaust A7 (abs)
Red alarm. Initiated by EMU.
Cause
Individual exhaust gas
temperature of this cylinder is too
high.
112708 – HIHI T-Exhaust A8 (abs)
Red alarm. Initiated by EMU.
Cause
Individual exhaust gas
temperature of this cylinder is too
high.
112709 – HIHI T-Exhaust A9 (abs)
Red alarm. Initiated by EMU.
Cause
Individual exhaust gas
temperature of this cylinder is too
high.
112710 – HIHI T-Exhaust A10 (abs)
Red alarm. Initiated by EMU.
Cause
Individual exhaust gas
temperature of this cylinder is too
high.
72 | Troubleshooting | MS150122/00E 2015-07
Corrective action
1. Check emission values.
2. Check ignition timing (→ Page 143).
3. Check valve drive (exhaust valves do not close).
Corrective action
1. Check emission values.
2. Check ignition timing (→ Page 143).
3. Check valve drive (exhaust valves do not close).
Corrective action
1. Check emission values.
2. Check ignition timing (→ Page 143).
3. Check valve drive (exhaust valves do not close).
Corrective action
1. Check emission values.
2. Check ignition timing (→ Page 143).
3. Check valve drive (exhaust valves do not close).
Corrective action
1. Check emission values.
2. Check ignition timing (→ Page 143).
3. Check valve drive (exhaust valves do not close).
Corrective action
1. Check emission values.
2. Check ignition timing (→ Page 143).
3. Check valve drive (exhaust valves do not close).