Control Inputs And Outputs; Speed Sensor Input Em-Enc; Termination Resistor - BONFIGLIOLI actice Instruction Manual

Table of Contents

Advertisement

5
5.1
The four speed sensor inputs of the EM-ENC-03 expansion module can be set via the
parameter
operation mode for the evaluation of a unipolar 24V two-channel speed sensor (incre-
mental speed sensor).
0 -
4 -
104 -
Unlike the standard sockets available according to specification RS-422A / RS-485, the
interface is suitable for a 5 V push-pull signal.
5.1.1
The termination resistor of 150 Ω for the speed sensor of the EM-ENC-03 speed sensor
is deactivated by default.
Caution!
OFF -
ON -
Note:
06/05
06/05

Control inputs and outputs

Speed sensor input EM-ENC

Operation mode Speed sensor 2
Operation mode
Off
Quadruple evaluation
Quadruple evaluation
inverted

Termination resistor

The termination resistor may only be activated for a 5 V push-pull signal
according to specification RS-422A / RS-485.
For activating the termination resistor, both slide switches S3 must be
set to "ON" position. Setting both slide switches to different positions may
destroy components.
If an unipolar speed sensor is used, e.g. with a 24V signal, no termination
resistor is required.
S3
Operation mode of switches S3
no termination resistor
termination resistor
With the two switches
interface is configured (refer to chapter "System Bus Interface").
493 and selection of the corresponding
Function
Speed measurement not active
Two-channel speed sensor with recognition of direction
of rotation via track signals A and B;
four signal edges are evaluated per division mark.
As operation mode 4; the actual speed value is in-
verted.
(Alternative to exchanging the track signals).
X410A
X410B
OFF (to the right)
ON (to the left)
S1
and S2, the bus connection of the system bus
S1
S2
Function
49