14.0 Installation Label - Bosch D6412 Operation And Installation Manual

Hide thumbs Also See for D6412:
Table of Contents

Advertisement

14.0 Installation Label

D6412
Bosch Security Systems recommends
testing the entire system at least once
a week, and having a qualified
technician check the system at a
minimum of once every 3 years.
Suitable for the following applications: 1) Household Burglar Alarm System Units, Grade A. 2) Household Fire Warning System Units. 3) Police Station
connect, Grade A Mercantile Premise alarm system, Grade A Mercantile Safe and Vault alarm system and Grade AA Mercantile Safe and Vault alarm system
when installed in conjunction with Model D8122 derived channel subscriber terminal unit. For all Police Station applications and grades, Model D8108A Attack
Resistant Enclosure with a UL Listed local sounding device is required. 4) Local, Grade A Mercantile Premise alarm system and Grade A Mercantile Safe and
Vault alarm system. For all local applications and grades, Model D8108A Attack Resistant Enclosure and a UL Listed local sounding device is required.
5) Central Station, Grade C application. Central Station, Grade B when installed with a UL Listed local sounding device. Central Station, Grade AA when
installed with Model D8122 derived channel subscriber terminal unit. 6) Proprietary Burglar Alarm units, Grade A. Proprietary Burglar Alarm unit,
Grade BB when installed with the Model D8122 derived channel subscriber terminal unit.
D6412 must be installed in accordance with D6412/D4412 Installation Instructions (P/N:45349).
Do not connect to a receptacle
controlled by a switch. Do not
share with
D6412 uses a
other
CX4010 UL Listed
equipment.
Class 2 Transformer
18 VAC 22 VA 60 HZ
Earth Ground
Green
Data
Yellow
Data
Aux Pwr -
Black
Red
Keypads, Expanders
Printer modules &
Communication modules
Aux
(up to 19 total devices)
Pwr
+
P
P
P
P
S
S
S
S
A
B
C
D
Supervised with 2.2 kΩ
EOL Resistor
(P/N: 47819).
PO4
Typical Initiating Devices
are Door Contacts NO/NC,
Floor Mats, Motion
Sensors, Glass Break
Outputs PO3 &
Detectors, etc.
PO4 can sink up
to 500 mA 12
VDC. Use D133/
Maximum charging
D134 for larger
current is 1.1 A.
loads.
BATTERY: Replace
every 3 to 5 years.
Use Bosch Security
Systems Model
Output PO2 can be used
D126, 12 V 7 Amp HR
with Alarm+ as a
Sealed Lead Acid
supervised siren driver.
Battery for Burglary or
Connect an approved
Combination Fire and
4 or 8 Ω siren.
Burglary Systems. For
Alternatively, PO2 can
additional load or
sink up to 500 mA 12
standby power, refer
VDC. Use D133/D134
to battery calculation
for larger loads.
sheet in D6412/D4412
Installation Instructions
(P/N:45349).
* Not investigated by UL.
WARNING: THIS UNIT INCLUDES AN ALARM VERIFICATION FEATURE FOR L-1 (LOOP 1)
THAT RESULTS IN A DELAY OF THE SYSTEM ALARM SIGNAL WHEN PROGRAMMED
FOR THIS FEATURE. THE TOTAL DELAY (CONTROL UNIT PLUS SMOKE DETECTORS)
SHALL NOT EXCEED 60 SECONDS. NO OTHER INITIATING DEVICES SHALL BE
CONNECTED TO LOOP 1 WHEN PROGRAMMED FOR ALARM VERIFICATION, UNLESS
APPROVED BY THE LOCAL AUTHORITY HAVING JURISDICTION.
© 2003 Bosch Security Systems
This system should be installed in accordance with the National Electrical Code, NFPA 70, the National Fire Alarm
Code, NFPA 72 and the local authority having jurisdiction. Depending on the application, the installation is to be in
accordance with one or more of the following UL standards: UL681 Installation and Classification of Mercantile and
Bank Burglar Alarm Systems; UL1076 Proprietary Burglar Alarm Systems and Units; UL1641 Installation and
Classification of Residential Burglar Alarm Systems. Printed information describing proper installation, operation,
testing, maintenance, repair service and response to an alarm is to be provided with this equipment.
Warning: Owner's Instruction Notice: Not to be removed by anyone except occupant.
This equipment has been type tested and found to comply with the specifications in Part 15 of FCC rules for Class B
Computing Devices. Operation is subject to the two following conditions (1) this device may not cause any interference,
and (2) this device must accept any interference received including interference that may cause undesired operation.
Complies with Part 68, FCC Rules. FCC Registration Number: ESVMUL-46531-AL-E
All external connections are inherently Class 2 power limited.
System Delay Chart
Smoke Detector
Circuit
Control Unit
(Loop)
Delay - Sec
Model
Delay - Sec
(a)
1
16 sec
(a) The delay (power-up) (start-up) time marked on the
installation wiring diagram of the smoke detector or
on the installed smoke detector(s) is to be used.
Auxilliary Powered Devices 11.5 to 12.4 VDC. Below 10.2 VDC, the D6412 stops processing Loop inputs.
With 7.0 Ah battery,
120 mA for 24 hrs for Fire and Combined Fire/Burglary,
400 mA for 4 hrs for UL Burglary.
600 mA for other*
Include keypads in calculations.
POWER SUPPLY REQUIREMENTSThe Power Supply provides a maximum of 600 mA
for the Control Panel and All Accessory Devices. For System loading, See D6412/D4412
Installation Instructions (P/N:45349). Requirements for battery standby time may reduce
allowable output.
CAUTION: See D6412/D4412 Installation Instructions (P/N:45349) for power
requirements relating to terminals [Alrm+] and [+Aux].
Installer
JP2
Keypad
Connect
Lock
PO1 Terminals can be configured
Installer
as an alarm power output. JP2-
Switch to
PO1 Jumper must be closed.
program.
+
-
Alrm
PO1
PO3 PO2
A
B
L-1
+
1
-
+
see
Note 1
Use compatible
Powered Sensor Loop
NAC such as
suitable for Two-Wire
Bosch Security
Smoke Detectors 2.2 kΩ
Systems D440
Resistor required at End of
Line. For compatible smoke
400 mA for Fire and
detectors, see D6412/D4412
Combined Fire/
Technogram (P/N:46928). The UL Panel
Burglary;
P/N
Compatibility Identifier = B. Also available for Four-
1500 mA for UL
25899
Wire Smoke Detectors such as Bosch Security Systems
Burglary;
D273TH.
1850 mA for other*
Applies to all four outputs combined.
D6412/D4412 Operation and Installation Guide
See D6412/D4412 Installation Instructions
(P/N:45349) for System Wiring Diagram
Installer Switch
Disables Arming,
Reports, and Relays.
Lock for local
programming.
Note 1: A supervisory alarm output module must be used
on these terminals for household fire applications
Note 2: Jumper J2-PO1 must be in place for connection
to NAC or other powered alarm device.
Com
L-2
L-3
Com
L-4
L-5
Com
2
3
4
5
Supervised Loops
Open
7.7 to 14.0 VDC
Normal
6.3 to 7.3 VDC
Short
0.0 to 6.0 VDC
2.2 kΩ Resistor
(P/N:47819)
Required at End of Line
Page 59
D6412/D4412
Installation Label
0.1B
Red
R
R
R1
R1
Gray
T1
T1
Brown
T
T
Green
Use Bosch
Security Systems
D164
Phone Cord
or equivalent.
Ground Start
requires
L-6
L-7
Com
L-8
D133/D134.
6
7
8
Minimum system requirements for Classification in
Accordance with ANSI/SIA CP-01-2000:
UL Listed and Classified control unit Model D6412;
UL Listed and Classified keypad, one or more of
the following:
D621(W), D623(W), D625(W);
UL Listed Local Bell.
This box will be checked if L-1 is
programmed for Alarm Verification.
P/N:48259G 10/02
© 2002 Bosch Security Systems
Premises
Phone
Incoming
Phone
Line
45349E