10.0 Off-Board Outputs

10.1

Overview

You can expand the total number of programmable outputs to twenty for the D6412 (twelve for the D4412) using the
DX3010 Octo-Output Module (two required for twenty outputs) or DX3020 Module. Instructions for the DX3010 Module
are included in this guide (as well as with the module). The DX3020 Module emulates two DX3010 Modules with the D6412
(emulates one with the D4412). DX3020 specific instructions are included with the module.
10.2

DX3010 Octo-Output Module

10.2. 1
Overview
The DX3010 Octo-Output Module allows you to add outputs to your system in groups of eight. You can add up to two
DX3010 Octo-Output Modules to the D6412 (one to the D4412). Combining the four on-board programmable outputs
with two DX3010 Octo-Output Modules (one on the D4412) makes a total of twenty programmable outputs available for
the D6412 (12 for the D4412). Review Section 5.0 Power Outputs to be sure you provide enough power for the Octo-Output
Modules and any other powered devices you connect to the panel.
You can assign any of the programmable output functions to the Octo-Output Module's individual outputs separately. See
Outputs in the D6412/D4412 Program Entry Guide (P/N: 45351) for programming details.
The DX3010 relay outputs are not supervised and cannot be used in fire or combined fire/burglary installations for
primary indicating devices.
IMPORTANT
Current Draw: 10 mA Standby plus 40 mA for each energized output (relay) for a total of 330 mA maximum with all eight
outputs energized.
Refer to the DX3010 Installation Guide (P/N: 46925) for complete installation, addressing, and operating instructions.
10.2.2

Configuring the DX3010 Octo-Output Module

Outputs may activate when setting the DX3010's switches, programming the panel, resetting the panel or applying
power to the panel. You may want to disconnect equipment connected to outputs while performing these functions.
10.2.3

Relay Outputs

Each DX3010 output provides a Form "C" dry contact rated for 5.0 A at 28 VDC. Normally-open, common, and normally-
closed terminals are available for each relay output. When an individual output is activated, there is continuity between the
normally-open and common terminals. When the output is not activated, there is continuity between the normally-closed
and common terminals.