SDI Devices
12.3.4

Configuration Jumpers

P2 – Diagnostic LED Pins
The diagnostic LEDs can be used for troubleshooting
purposes. See Figure 40 for jumper plug placements.
The DX4010 draws more current when the
diagnostic LEDs are enabled. Do not enable the
diagnostic LEDs under normal operating
conditions.
• BUS RX LED: SDI bus receives data from control panel.
• BUS TX LED: SDI bus transmits data to control panel.
• SER RX LED: RS-232 receives data from printer (or other serial device connected to DX4010).
• SER TX LED: RS-232 transmits data to printer (or other serial device connected to DX4010).
P3 – RS-232 Cable Ground Pins
Some devices connected to the DB9 connector may cause a ground fault condition on the control panel. If this occurs,
removing the plug across the P3 jumper pins may clear the ground condition.
Some devices can cause a ground fault even if the P3 jumper plug is removed.
• P3 Jumper Pins Disabled: Isolate DB9 Shield from SDI Common (Black)
• P3 Jumper Pins Enabled: Connect DB9 Shield to SDI Common (Black)
Address DIP Switches
Use the address DIP switches to assign Address 250 to the
DX4010 when a serial device is connected to it. Set the DIP
switches to Address 0 (zero) when preforming a remote
programming direct connection. See Figure 41 for proper
DX4010 DIP Switch positioning, and Table 18 for DX4010
address settings.
12.3.5

Supervision

Supervision includes operation of the SDI bus, printer paper supply, and serial printer (or device) selected (on-line). The
panel sends an SDI Missing Report if it fails to communicate with the DX4010 Module.
12.3.6

DX4010 Module's DB9 Connector

The DB9 pins are configured as shown in Figure 42.
1 - DCD
2 - RxD
3 - TxD
45349E
DIP Switches
S1
Module Address
1
0
ON
250
ON

Table 18: DX4010 Address Settings

4 - DTR
7 - RTS
5 - GND
8 - CTS
6 - DSR
9 - RI

Figure 42: DX4010 D89 Connector Layout

D6412/D4412 Operation and Installation Guide
Diagnostic LED Pins (P2)
Disabled
Enabled

Figure 40: DX4010 P2/P3 Jumper Pin Settings

Address 0 (zero) Settings
ON
1
2
3
4
1
2
4
8

Figure 41: DX4010 DIP Switch Orientation

DIP Switch Settings
S2
S3
S4
S5
2
4
8
16
ON
ON
ON
ON
ON
ON
ON
ON
1 2
3 4
6 7 8 9
Page 52
Cable Ground Pins (P3)
Disabled
Enabled
OFF
5
6
16
M
O
D
E
S6
Mode
OFF
ON
5
© 2003 Bosch Security Systems
ON