R911299722 / 02 | Rexroth IndraControl VCP 20

Dimensions

5
Dimensions
5.1

Installation

Electric Drives and Controls | Bosch Rexroth AG
When installing the operator terminal, keep a minimum clearance of
30 mm (1.181") around the operator terminal to ensure adequate air cir-
culation.
When the operator terminal is installed horizontally, please note that ad-
ditional sources of heat beneath the operator terminal may result in heat
accumulation.
Provide for sufficient heat dissipation!
Comply with the allowable temperature range listed in the technical data
for the use of the operator terminal!
To maintain the specified degree of protection, make sure the seal is
evenly seated on the installation surface and the brackets tightened uni-
formly.
The operator terminal can be easily and quickly mounted from the rear
of the operator terminal. This is particularly recommended for mounting
in switchboards with a plate thickness of approx. 1 mm to 10 mm
(approx. 0.039" to 0.394").
1. Insert the operator terminal from the front through the mounting cut-
out.
2. Fasten the operator terminal using brackets.
5-1