Keyswitch Installation; Keyswitch Operation; Figure 34: Keyswitches - Bosch D6412 Operation And Installation Manual

Hide thumbs Also See for D6412:
Table of Contents

Advertisement

D6412/D4412
Arming Devices
11.4.3

Keyswitch Installation

For maintained switches, connect the EOL resistor for the point at the keyswitch so the switch opens the circuit when it
operates. A short on the circuit produces an alarm if the area is armed and a trouble if it is disarmed (see Figure 34).
For momentary switches, connect the EOL resistor for the point at the keyswitch so the switch shorts the resistor when it
operates. If the area is armed, an open on the circuit produces an alarm; and when the area is disarmed, an open on the
circuit produces a trouble (see Figure 34).
Maintained Keysw itch
Common
Point Inpu t
11.4.4

Keyswitch Operation

Arming/Disarming
The panel offers a wide variety of keyswitch arming options. See Point Index Configuration in the D6412/D4412 Program
Entry Guide (P/N: 45351) for details on configuring keyswitch arming options.
Silencing Alarms
• Momentary Keyswitch: To silence alarms (stop Alarm output), operate the keyswitch. If the area is armed,
operating the keyswitch to silence the alarm also disarms the area. If the area is disarmed, operating a
momentary keyswitch to silence the alarm does not arm the area.
• Maintained Keyswitch: If the area is armed, turn the keyswitch to the disarmed position. The panel disarms the
area and silences the alarm. If the area is disarmed, turn the keyswitch to the armed position (the panel does not
arm) and return to the disarmed position.
45349E
Open o n
Circuit
2.2 K
Arm s Area

Figure 34: Keyswitches

D6412/D4412 Operation and Installation Guide
Page 48
Momentary Keyswitch
Co mmon
2 .2 K
Point Input
Sho rt on
Circuit
Tog gles
Arm ing Sta te
© 2003 Bosch Security Systems

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

D4412

Table of Contents