6 Installation
Fig.13
Room-ventilated version
Fig.14
Room-sealed version (concentric)
26
6.5.4 Length of the air and flue gas pipes
With a room-ventilated version, the air supply opening stays open; only the
L
flue gas outlet opening is connected. This will ensure that the boiler ob
=
tains the necessary combustion air directly from the installation area.
Tab.13 Maximum chimney length (L)
AD-0000028-01
With a closed version, both the flue gas outlet and the air supply openings
are connected (concentrically).
L
=
Tab.14 Maximum chimney length (L)
AD-0000029-01
Note
When using bends, the maximum chimney length (L) must be
shortened according to the reduction table.
The boiler is also suitable for longer chimney lengths and diam
eters other than those specified in the tables. Contact us for
more information.
Room-ventilated version (B23, B23P, B33)
Flue gas outlet connection
Air supply connection
Caution
The air supply opening must stay open.
The installation area must be equipped with the necessary air
supply openings. These openings must not be obstructed or
shut off.
Quinta Pro
80 mm
30
40 m
45
33 m
65
10 m
90
9 m
115
8 m
Room-sealed version (C13, C33, C43, C63, C93)
Flue gas outlet connection
Air supply connection
Quinta Pro
30
45
65
90
115
Diameter
90 mm
100 mm
40 m
40 m
40 m
40 m
18 m
27 m
16 m
24 m
12 m
19 m
Diameter
80–125 mm
100–150 mm
20 m
20 m
16 m
20 m
-
13 m
-
13 m
-
7 m
123157 - v.07 - 10082015
110 mm
40 m
40 m
40 m
40 m
37 m