6.6.3 Access to the connectors
Various thermostats and regulators can be connected to the standard PCB
(PCU) (connector X12).
Access to the connectors:
1. Unscrew the two screws located under the front housing by a quar­
2. Guide the cables from the regulator or the thermostat through the
90º
3. Tilt the instrument box forwards by opening the clips on the sides.
4. Open the instrument box by opening the clip on the front.
1
5. Guide the relevant connection cable(s) through the instrument box
6. Unscrew the strain relief clamps as required (in front of the connec­
7. Connect the cables to the appropriate terminals on the connector.
3
8. Screw the strain relief clamps securely into position and close the
7
X12
X13
AD-3000075-01
Caution
Separate the sensor cables from the 230 V cables.
ter turn and remove the front housing.
round grommet(s) on the right-hand side of the boiler bottom plate.
via the grommet(s) provided.
tor) and guide the cables underneath.
control panel.
123157 - v.07 - 10082015