10 Maintenance
Fig.58
Checking flue gas outlet/air supply
connections
60

10.3.2 Checking the ionisation current

1. Check the ionisation current at full load and at low load.
The value is stable after 1 minute.
2. Clean or replace the ionisation/ignition electrode if the value is lower
than 4 µA.
For more information, see
Replacing the ionisation/ignition electrode, page 64

10.3.3 Checking the flue gas outlet/air supply connections

1. Check the flue gas outlet and air supply connections for condition
and tightness.
AD-0000084-01

10.3.4 Checking the combustion

Combustion is checked by measuring the O
gas outlet duct.
/CO
percentage in the flue
2
2