red LED signal (*) code and symbol
on display
(fl ashing)
2 fast fl ashes
Et
-
5 fast fl ashes
EP
3 fast fl ashes
EF
4 fast fl ashes
Ed
5 slow fl ashes
CL
6 fast fl ashes
PU
-
2 slow fl ashes
H^
3 slow fl ashes
H_
4 slow fl ashes
EE
1 fast fl ash
E0
7 slow fl ashes
OFL
8 fast fl ash
EL
To reset the alarms, press ESC once to mute the buzzer, press ESC a
second time to completely reset the alarm.
(*) Fast fl ash: 0.2 seconds ON and 0.2 seconds OFF
Slow fl ash: 1 second ON and 1 second OFF

9. ALARMS

meaning
cause
Autotest failed
- Fill not connected or
insuffi cient
- drain open
- faulty fl oat
No production
Malfunction of
fi ll SV leak
piezoelectric transducers
fan malfunction
No water
Interruption to water
supply or fi ll solenoid
valve malfunction
No drain
Drain solenoid valve/
circuit malfunction
Tank maintenance
1500 operating hours
request signal
for recommended
maintenance exceeded
External control
Cable interrupted/
signal not connected
disconnected/not
correctly
connected correctly.
High humidity
The signal from the
probe indicates humidity
above 80%rH
Low humidity
The signal from the
probe indicates humidity
less than 20%rH
EEPROM alarm
Problems in the EEPROM If the problem persists,
Functional test not
Functional test
performed
not performed by
manufacturer/EEPROM
problems
Master Offl ine
Loss of connection from
the serial master
(If D37=1)
Water level alarm
Level too high during
atomised water
production due to:
fi ll SV leak
transducer
malfunction
fan malfunction
solution
Check:
yes
water supply and fi ll
valve;
blockage of fi lter on
fi ll solenoid valve;
check drain solenoid
valve and drain
connection;
Carry out maintenance
yes
on tank
Check:
yes
water supply and fi ll
(in the 10
valve;
minute
blockage of fi lter on
waiting
fi ll solenoid valve
period)
Check drain valve and
yes
drain connection
Carry out maintenance
no
on tank and transducers
Check the reference
yes
signal (4 to 20 mA or 2
to 10V).
Check humidity probe
yes
signal/cable
Check humidity probe
yes
signal/cable
yes
contact the CAREL
service centre
If the problem persists,
yes
contact the CAREL
service centre
Check state of the
yes
Master / Cable
Check:
yes
fi ll SV
transducers
fans
Direct version for room applic. +0300062IE - rel. 1.0 - 10.09.2015
25
alarm relay
action
activation
humidifi cation
ESC / Digital 29
interrupted
humidifi cation
ESC / Digital 29
interrupted
humidifi cation
automatic (after
interrupted
10 minute wait)
only per 10
minutes
humidifi cation
ESC / Digital 29
interrupted
signal only
Reset hour
counter
humidifi cation
AUTO
interrupted
humidifi cation
AUTO
interrupted
humidifi cation
AUTO
interrupted
humidifi cation
If this persists
interrupted
contact service
humidifi cation
If this persists
interrupted
contact service
humidifi cation
AUTO
interrupted
humidifi cation
AUTO
interrupted
ENG
reset
Tab. 9.a