8. HUMIDIFIER CONTROL VIA NETWORK

The variables shown in the list are a set of all the internal variables. DO
NOT CONFIGURE ANY VARIABLES THAT ARE NOT SHOWN IN THE TABLE,
OTHERWISE HUMIDIFIER OPERATION MAY BE AFFECTED.
The serial connection (M11) is confi gured by default with the following
parameters:
- Address 1
- Baud rate 19200 bps
- Frame 8,N,2

8.1 Supervisor variable list

"A"
analogue variables* (Modbus®: REGISTERS)
CAREL - Modbus®
1
param. d0: Th probe temperature reading
2
param. d1: Th probe humidity reading
3
param. d2: Probe reading
4
param. d5: Set point trimmer reading
"I"
integer variables (Modbus®: REGISTERS)
CAREL
Modbus®
1
129
Level access password
2
130
Firmware release
15
143
Alarms, see Cap. "ALARMS":
bit0: E0 Alarm
bit1: Et Alarm
bit2: EF Alarm
bit3: Ed Alarm
bit4: EP Alarm
20
148
Parameter A0: Operating mode
21
149
Parameter A2: Type of external sensor
22
150
Parameter A3: Probe minimum
23
151
Parameter A4: Probe maximum
24
152
Parameter A5: Probe off set
25
153
Parameter A6: Fan off delay time
26
154
Parameter A7: Fan speed
27
155
Parameter A8: Maximum evaporation time for no production alarm
28
156
Parameter A9: Minimum evaporation time for no production alarm
29
157
Parameter b0: Operating options
30
158
Parameter b1: Time between two washing cycles
31
159
Parameter b2: Inactivity time for washing on next start
32
160
Parameter b3: Washing time (fi ll + drain)
33
161
Parameter b4: Start delay time
34
162
Parameter b5: Operating hours for CL alarm
35
163
Parameter b6: Time to display new CL alarm in minutes
36
164
Parameter b7: Transducer On/Off control interval
37
165
Parameter b8: Probe delay disconnected
38
166
Reserved
39
167
Parameter bA: Maximum fi ll time
40
168
Parameter bb: Refi ll time in evaporation
41
169
Parameter bC: Maximum drain time
42
170
Parameter bd: Drain opening time to completely empty tank
43
171
Parameter bE: Delay time after measuring low level for refi lling
44
172
Parameter C0: Default display (Terminal)
45
173
Parameter C1: Parameter A0: Baud rate
46
174
Parameter C2: tLAN address (If 0 Master controller)
47
175
Parameter C3: Serial address
48
176
Parameter P0: Maximum fl ow-rate
49
177
Parameter P1: Humidity control hysteresis
50
178
Parameter P2: Low humidity alarm threshold
51
179
Parameter P3: High humidity alarm threshold
52
180
Parameter SP: Humidity set point
53
181
Parameter d3: Operating hour counter
54
182
Parameter d4: Unit hour counter (not resettable)
60
188
Serial request (If digital 37 is setted)
65
192
Parameter C4: Timeout for offl ine master serial
87
215
FW release slave 1
88
216
Instantaneous production slave 1
89
217
Slave 1 status
90
218
Phase slave 1
91
219
Alarm mask slave 1
92
220
Hour counter operation slave 1
93
221
FW release slave 2
94
222
Instantaneous production slave 2
95
223
Slave 2 status
96
224
Phase slave 2
97
225
Alarm mask slave 2
98
226
Hour counter operation slave 2
99
227
FW release slave 2
100
228
Instantaneous production slave 3
101
229
Slave 3 status
102
230
Phase slave 3
bit5: PU Alarm
bit6: H ¯ Alarm
bit7: H_ Alarm
bit8: EE Alarm
bit9: CL Alarm
23
Direct version for room applic. +0300062IE - rel. 1.0 - 10.09.2015
ENG
R/W
R
R
R
R
R/W
R/W
R
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R
R/W
R/W
R/W
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R