integer variables (Modbus®: REGISTERS)
CAREL
Modbus®
103
231
Alarm mask slave 3
104
232
Hour counter operation slave 3
"D"
digital variables (Modbus®: COILS)
CAREL - Modbus®
2
Just started fl ag
3
Humidifi er ready to produce
4
Humidity set point reached
5
Green LED
6
Red LED
7
Yellow LED
8
Remote On/Off
9
Low level
10
High level
11
Aux level
12
Autotest completed
14
BMS serial in tLAN mode
15
Reserved
16
Reserved
17
Terminal connected
18
Production in progress
19
Fill
20
Drain
21
Transducer 1
22
Transducer 2
23
Fan
24
Alarm relay
25
Auxiliary relay
26
Manual drain
27
Disable from serial
28
Reset hour counter
29
Reset alarms
30
Washing due to inactivity activated
31
Functional test performed
33
Unit of measure
37
Serial control enable
38
Activate wash from serial

8.2 Production control via network

To control production via a he connection, confi gure the humidifi er using
following parameters:
Digital 27, Digital 37 and Integer 60 (Modbus 188)
When the D37 is at 1, the humidifi er excludes the external command
signals (external regulator or probes) and uses the value of Integer 60
(modbus 188) as like comand signal. The humidity production can be
managed in two modes:
To manage the production level in percentual mode:
Set D 37 = 1;
Set parameter A0 = 1 (Carel 20, Modbus 148, Proportional Mode);
Set integer variable 60 Carel (188 Modbus) to the desired level
(0-1000 = 0-100.0%).
To manage the production with a humidity probe managed by the
master:
Set D 37 = 1;
Set parameter A0 = 2 (Carel 20, Modbus 148, Humidity probe Mode);
Set integer variable 60 Carel (188 Modbus) to the desired level
(0-1000 = 0-100.0 rH%);
Set integer variable 52 Carel (180 Modbus) to the desired humidity
setpoin.
When the D37 is at 1, if the communication is lost for the seconds settled
by parameter C4, is generated the "Master Offl ine" alarm (see alarms
table) and the production stops.
Production is activated/deactivated via digital parameter D27 (see
parameter table).
If D27 = 1 the humidifi er is disabled and production stops
if D27 = 0 the humidifi er is enabled and production is activated.
D27 is independent from the state of D37.
Direct version for room applic. +0300062IE - rel. 1.0 - 10.09.2015

8.3 Washing cycle activation via network

A washing cycle can be performed at any time by managing digital
variable 38.
Setting the variable to 1 will immediately activate a washing cycle, even
if the unit is in standby, and even if both automatic washing and washing
due to inactivity are disabled by their corresponding parameters.
The variable will keep the value 1 throughout the duration of the washing
cycle, and will automatically be reset at the end of the cycle.
24
R/W
R
R
Tab. 8.a
R/W
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R/W
R/W
R/W
R/W
R
R
R/W
R/W
R/W
Tab. 8.b