Optional Receptacle Panel Installation Instructions
These are the instructions for installing the optional Modular Output Receptacle Panels for the 1600EP
Series UPS. These instructions apply to all UE3-RP-XX panel options.
WARNING: The work outlined in these instructions is to be performed only on a completely un-energized
UPS system.
Please refer to Figure 1 for location of UPS referenced material. Refer to Figure 2 for material referring
to the receptacle panel module.
Step 1: Remove modular receptacle panel cover plate
On the rear of the UPS, locate the cover plate for the receptacle panel module interface
(see Figure 1).
Remove the 6 mounting screws.
Remove the cover plate. A square-shaped "plug" will appear exposed near the upper-left corner
of the uncovered slot.
Step 2: Snap-In Output Receptacle modular panel
Carefully mate the square-shaped connector on the UPS to its matching counter part on the rear of the
modular panel.
Step 3: Mount the receptacle panel
Attach the screws removed from the cover plate through the mounting holes of the receptacle panels and
back into the UPS mounting points.
Mounting
Screws
Figure 1
50
Figure 2
1600EP Series Instruction Manual